10
Preparing for installation
Model name for combination
AM580HXVAGH1 AM600HXVAGH1 AM620HXVAGH1 AM640HXVAGH1 AM660HXVAGH1 AM680HXVAGH1
Number of individual outdoor units
3
3
3
3
3
4
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
2
AM140FXVAGH
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
2
2
2
2
3
2
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
163.2
168.2
173.6
179.2
184.8
190.4
Heating (kW)
183.6
189.0
195.3
201.6
207.9
214.2
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
81.6
84.1
86.8
89.6
92.4
95.2
Maximum (kW)
212.3
218.7
212.3
233.0
240.2
247.5
Maximum number of connectable
indoor units
64
64
64
64
64
64
Model name for combination
AM700HXVAGH1 AM720HXVAGH1 AM740HXVAGH1 AM760HXVAGH1 AM780HXVAGH1 AM800HXVAGH1
Number of individual outdoor units
4
4
4
4
4
4
Combined outdoor
unit
AM080FXVAGH
AM100FXVAGH
AM120FXVAGH
1
1
1
1
1
AM140FXVAGH
1
1
AM160FXVAGH
1
AM180FXVAGH
1
AM200FXVAGH
1
AM220FXVAGH
2
2
2
2
3
3
AM240HXVAGH
AM260HXVAGH
Rated capacity
Cooling (kW)
196.8
201.8
207.2
212.8
218.4
224.8
Heating (kW)
221.4
226.8
233.1
239.4
245.7
252.9
Total capacity of the
connected indoor
units (Cooling)
Minimum (kW)
98.4
100.9
103.6
106.4
109.2
112.4
Maximum (kW)
255.8
262.3
269.4
276.6
283.9
292.2
Maximum number of connectable
indoor units
64
64
64
64
64
64
Summary of Contents for DVM S AM080FXVAGH