21
ENGLISH
Space requirement for installation
f
Space requirement was decided based on following conditions; Cooling mode, outdoor temperature of 35 °C. Larger
space is required if the outdoor temperature is higher than 35 °C or if the place is heated easily by quantity of solar
radiation.
f
When you secure installation space, consider path for people and the direction of the wind.
f
Secure installation space as shown in the below illustration, considering ventilation and the service space.
f
If the installation space is narrow, installer or other worker may get injured during work and may also cause problem to
the product.
f
If you install multiple number of outdoor units in one space, make sure to secure enough ventilation space if there’s
any walls around the product that may disturb the air flow. If enough ventilation space is not secured, product may
malfunction.
f
You may install the outdoor units with 20mm of space between the product, but product’s performance may decrease
depending on the installation environment.
Single installation
(Unit : mm)
Height of the wall is
unlimited
O
ver 100 (S2)
O
ver 500 (S1)
Over 100
Over 100
Front
side
Over 100
Over 300
<Case 1>
<Case 2>
Front side