71
ENGLISH
Selecting solderless ring terminal
f
Select a solderless ring terminal for a power cable according to the nominal dimensions for cable.
f
Apply insulation coating to the connection part of the solderless ring terminal and the power cable.
Silver solder
Nominal dimensions for cable (mm
2
)
4/6
10
16
25
35
50
70
Nominal dimensions for screw (mm)
4
8
8
8
8
8
8
8
8
8
B
Standard dimension (mm)
9.5
15
15
16
12
16.5
16
22
22
24
Allowance (mm)
±0.2
±0.2
±0.2
±0.3
±0.3
±0.3
±0.4
D
Standard dimension (mm)
5.6
7.1
9
11.5
13.3
13.5
17.5
Allowance (mm)
+0.3
-0.2
+0.3
-0.2
+0.3
-0.2
+0.5
-0.2
+0.5
-0.2
+0.5
-0.2
+0.5
-0.4
d1
Standard dimension (mm)
3.4
4.5
5.8
7.7
9.4
11.4
13.3
Allowance (mm)
±0.2
±0.2
±0.2
±0.2
±0.2
±0.3
±0.4
E
Min. (mm)
6
7.9
9.5
11
12.5
17.5
18.5
F
Min. (mm)
5
9
9
13
15
13
13
13
14
20
L
Max. (mm)
20
28.5
30
33
34
38
43
50
51
d2
Standard dimension (mm)
4.3
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
8.4
Allowance (mm)
+ 0.2
0
+ 0.4
0
+ 0.4
0
+ 0.4
0
+ 0.4
0
+ 0.4
0
+ 0.4
0
+ 0.4
0
t
Min. (mm)
0.9
1.15
1.45
1.7
1.8
1.8
2.0
Summary of Contents for DVM S AM080FXVAGH