99
ENGLISH
Setting the Pipe Addresses Manually
You can use the wired or wireless remote control or the S-NET Pro 2 to set the pipe addresses for each indoor unit.
Setting by using the wired or wireless remote control (For how to operate the remote control
buttons, see the remote control user manual.)
1. Turn on both the indoor unit and the remote control.
2. Enter the “Option setting mode” on the remote control.
3. Set the address of each MCU port that is connected to an indoor unit by referring to the following table. (You can also set
the address of each indoor unit.)
Option
SEG1
SEG2
SEG3
SEG4
SEG5
SEG6
Value
0
A: Address setting
mode
0: The address of the
indoor unit will not
be set.
1: The address of
the indoor unit will
be set.
0 to 9: Hundreds
digit of the indoor
unit address
0 to 9: Tens digit
of the indoor unit
address
0 to 9: Units digit
of the indoor unit
address
Option
SEG7
SEG8
SEG9
SEG10
SEG11
SEG12
Value
1
0
0: The RMC address
will not be set.
1: The RMC address
will be set.
0
0 to F: RMC group
channel
0 to F: RMC group
address
Option
SEG13
SEG14
SEG15
SEG16
SEG17
SEG18
Value
2
0
0: The MCU address
will not be set.
1: The MCU address
will be set.
0 to 1: Tens digit of
the MCU address
0 to 9: Units digit of
the MCU address
A to F: MCU port
address
Option
SEG19
SEG20
SEG21
SEG22
SEG23
SEG24
Value
3
0
0
0
0
0
Examples> If the indoor unit whose address is not yet set is connected to port A on the MCU 1, set 0A0000-100000-
20101A-300000.
If the indoor unit whose address is set to 9 is connected to port B on the MCU 2, set 0A1009-100000-20102B-300000.
Setting by using S-NET Pro 2
f
Set the pipe addresses by using Add-on > Change address on S-NET Pro 2. (For more information, see the S-NET Pro 2
Help.)