Samsung Electronics
2-2 Product Specifications
Power Source
AC220V, 60Hz
Ventilation Mode
Heat-Ex Ventilation
By-Pass Ventilation
The Level of the Air Volume
Turbo
High
Low
Turbo
High
Low
Power Supply(W)
120
105
85
120
105
85
Air Volume(m³/h)
250
210
180
250
210
180
External Static Pressure(mmAq)
12.2
9.2
6.2
12.2
9.2
6.2
Temperature Exchange
Efficiency(%)
Cooling
69
71
73
-
-
-
Heating
81
83
85
-
-
-
Valid Heat Exchange
Efficiency(%)
Cooling
52
55
59
-
-
-
Heating
72
74
77
-
-
-
Size(widthxheightxdepth)(mm)
660 x 350 x 600
Weight(kg)
25.5
Duct Size(mm)
150
Air Volume Control Specifications (Turbo)
Range : External Static Pressure 5.0~12.2[mmAq], Power Supply 85.0~120.0[W]
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
3. Duct length refers to its size when friction loss coefficient stands at 0.02
■
RHF025EE
Power Source
AC220V, 60Hz
Ventilation Mode
Heat-Ex Ventilation
By-Pass Ventilation
The Level of the Air Volume
Turbo
High
Low
Turbo
High
Low
Power Supply(W)
115
100
85
115
100
85
Air Volume(m³/h)
350
300
260
350
300
260
External Static Pressure(mmAq)
17.0
12.1
9.0
17.0
12.1
9.0
Temperature Exchange
Efficiency(%)
Cooling
71
73
75
-
-
-
Heating
80
82
84
-
-
-
Valid Heat Exchange
Efficiency(%)
Cooling
54
57
60
-
-
-
Heating
71
74
77
-
-
-
Size(widthxheightxdepth)(mm)
1,012x270x1,000
Weight(kg)
42.5
Duct Size(mm)
200
Air Volume Control Specifications (Turbo)
Range : External Static Pressure 4.0~17.0[mmAq], Power Supply 68.0~115.0[W]
Trial Operation Conditions
1. Air Volume/ External Static Pressure, Comply with KS Heat Exhaust Ventilation System Standards(KS B6879).
2. Heat Exchange/Temperature Exchange Efficiency, Comply with regulations to pro-
mote high efficiency energy devices,
[Cooling], Indoor(24˚C DB/17˚C WB), Outdoor(35˚C DB/24˚C WB)
[Heating], Indoor(22˚C DB/13.9˚C WB), Outdoor(2˚C DB/0.44˚C WB)
3. Duct length refers to its size when friction loss coefficient stands at 0.02
■
RHF035EE
2-2
27723A(1)_RHF-025EB_1.indd 5
2007-05-09 ソタネト 4:23:00