Functions of Touch Centralized Controller
Menu within a zone
You can create a new page with the
beside the page number. However, the page without an indoor unit will be
automatically deleted with saving.
Icon
Function
Description
Deleting a page
You can delete the page which does not have devices.
•
You cannot delete the page that has devices.
CAUTION
Moving a zone You can move a selected device to another zone
Moving a page You can move a selected device to another page.
Grouping
You can make a group for the selected devices so that a user can view them as one group. When
the devices become a group, the last selected device will be the main device and be displayed
on the screen.
Individualizing You can individualize the devices that have become a group.
Changing a
device name
You can change the name of a device.
Save
Save the zone that a user has edited and the formation of devices.
- A user can change the order of devices with drag & drop within a page.
•
When there are 2 or more zones, the zone list will be displayed with control & monitoring. When there is one
zone, zone list will not be displayed with control & monitoring.
NOTE
8.
Trouble history
f
f
You can view the history of the errors with a device.
9.
DI pattern
f
f
You can define rules that operate according to the DI signal.
Pattern
Description of control
1
•
There is no function.
2
•
When DI-1 ON signal is input, emergency stop status will occur.
•
It will stop all indoor units and order the indoor units not to be controlled by a remote controller.
•
In the emergency stop status, you cannot use the user control command. In addition, the schedule control will
not work. When the contact control signal is changed to OFF, the control command can work normally. (DI-2
will not be used with the pattern 2)
3
•
When DI-1 ON signal is input, it will stop all indoor units. When OFF signal is input, all indoor units are ON.
•
When DI-2 ON signal is input, the remote control status of all the indoor units will be enabled and when the
OFF signal is input, the remote control status will be disabled.
4
•
It will operate when pulse signal is input to DI-1/2 as contact input.
•
When the pulse contact signal is input to DI-1, ON command will be sent to all indoor units.
•
When the pulse contact signal is input to DI-2, OFF command will be sent to all indoor units.