Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area.
1) Remove the caps from the 2-Way valve and
the 3-Way valve.
3) Set the unit to cool operation mode.
(Check if the compressor is operating.)
4) Turn the 2-Way valve clockwise to close.
7) Close the cap of each valve.
2) Turn the 3-Way valve clockwise to close and
connect a pressure gauge (low pressure side)
to the service valve, and open the 3-Way valve
again.
5) When the pressure gauge indicates "0" turn the
3-Way valve clockwise to close.
6)
Stop operation of the air conditioner.
14-6 "Pump down" Procedure
2-Way Valve
3-Way Valve
Relocation of the air conditioner
• Refer to this procedure when the unit is relocated.
•
1. Carry out the pump down procedure (refer to the details of ‘pump down’).
•
2. Remove the power cord.
•
3. Disconnect the assembly cable from the indoor and outdoor units.
•
4. Remove the flare nut connecting the indoor unit and the pipe.
• 4.
At this time, cover the pipe of the indoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
•
5. Disconnect the pipe connected to the outdoor unit.
• 4.
At this time, cover the valve of the outdoor unit and the other pipe using a cap or vinyl plug to avoid foreign
material entering.
•
6. Make sure you do not bend the connection pipes in the middle and store together with the cables.
•
7. Move the indoor and outdoor units to a new location.
•
8. Remove the mounting plate for the indoor unit and move it to a new location.
14-6-1 MH040FXEA2/MH052FXEA2/MH14
✳✳
2X/MH16
✳✳
2X/MH18
✳✳
2X/MH19
✳✳
2X
24296A(1)_2 11/11/05 5:07 PM Page 12-22
Summary of Contents for MH020FPEA
Page 84: ...MEMO 5 4 Samsung Electronics...
Page 90: ...MEMO 5 10 Samsung Electronics...
Page 95: ...Samsung Electronics 5 15 Exploded Views and Parts List 1 2 8 9 10 11 3 6 7 4 5 PK118MG...
Page 136: ...MEMO 6 32 Samsung Electronics...
Page 206: ...MEMO 15 10 Samsung Electronics...
Page 207: ...MEMO Samsung Electronics 15 11...