Control and Monitoring (Continued)
Indoor Unit Usage Restriction_Temperature Limit in Cool/Heat mode
You can set temperature lower/upper temperature limit in
cool/heat mode.
1
Click [Control and Monitoring]
[Indoor unit usage
restriction] when DMS2 web page menu screen appears.
2
Press [Edit] button.
3
Set the lower/upper temperature limit.
You can set lower/upper temperature limit by selecting
'Enable'/'Disable'.
If desired temperature is lower than lower limit
temperature when the indoor unit is operating in cool
mode, DMS2 controls indoor unit to lower temperature
limit.
If desired temperature is higher than upper limit
temperature when the indoor unit is operating in heat
mode, DMS2 controls indoor unit to upper temperature
limit.
Lower temperature limit range: 18
℃(
65
°F)
~30
℃(
86
°F)
Upper temperature limit range: 16
℃(
61
°F)
~30
℃(
86
°F)
If the indoor unit is in Auto(Cool)/Auto(Heat) mode, lower/
upper temperature limit will be applied when the indoor
unit is operating in Auto mode.
However, if the upper temperature limit is set to
16°C(61°F)~17°C(64°F), the upper temperature limit in
Auto(Heat) mode is 18°C(65°F).
ERV PLUS and Fresh duct cannot set the lower temperature
limit in Cool mode or upper temperature limit in Heat mode.
4
Click [Save].
Indoor unit usage restriction setting will be saved.