E-
15
Cable tie
LAN cable
Connect
communication
cable
Adapter
Installing the BACnet Gateway (Continued)
Connecting Interface Module
1
Unfasten the 2 screws on the bottom of the BACnet
Gateway front cover. Hold the bottom 2 sides of the
BACnet Gateway and push downwards to slide open the
cover.
2
Connect the adapter to the power terminal.
Arrange the adapter as the right figure.
3
Separate 1 terminal block from 5 terminal blocks which
are attached to RS485 communication terminal.
Then, connect
i
nterface module communication cable(R1,
R2) to the terminal block.(R1
A, R2
B)
4
Connect LAN cable to the Ethernet terminal of BACnet
Gateway. Then arrange it using cable tie.
5
Fasten the bottom cover of BACnet Gateway and fix it
using 2 screws.
Maximum 80
i
nterface modules can be connected to one
BACnet Gateway.