E-
78
Setting and Checking Watt-Hour Meter
3
EHP Power Consumption Inspection (Continued)
1
Click [EHP Power Consumption Inspection]
[Setting and checking watt-hour
meter] when DMS2 web page menu screen appears.
Setting watt-hour meter is possible only when SIM/PIM is installed.
2
Click [Edit] when the setting and checking watt-hour meter screen appears.
CT proportion ‘1’ is set as default.
3
Set name and CT proportion of watt-hour meter.
You can use maximum 16 letters.
The range of CT proportion value is positive number from 1 to 5000.
4
Click [Save].
Set watt-hour meter information will be saved in DMS2.
If you do not click [Save], changed setting will not be saved.
Watt-hour meter value shows actual value of currently connected watt-hour meter.
Watt-hour meter value will be updated automatically.
When using CT watt-hour meter, be careful that there can be difference with actual
power consumption as much as CT ratio error.
1
4
2