E-
136
Contact Control Pattern Selection
1
Click [System Settings]
£
[System environment setting]
when DMS2.5 web page menu screen appears.
2
Click [Edit] from contact point pattern selection window.
3
Select the pattern you want to check.
X
Pattern 1[No external input]:
No operation will be made when inputting contact control
signal.
X
Pattern 2[Level(Emergency stop)]:
Commands that stop all operation of indoor unit and
disable remote control when inputting contact control
signal. In level emergency stop status, it will not be
controlled even if the command is from upper controller.
X
Pattern 3[Level(Operation
/
Stop)]:
Level signal input timing.
It changes operation/stop status of all indoor units.
X
Pattern 4[pulse (Operation
/
Stop
,
Disable/Enable)]:
Pulse signal. It changes operation/stop status of all indoor
units.
4
Click [Save] after setting is completed.
3
1
2
4
System Settings (Continued)