E-
96
■
Control logic is used in the following situations.
Ex) The current temperature of the lab is higher than 29
°C
and you want cooling operation,
The current temperature of the office is lower than 10
°C
and you want heating operation
■
Period, day and time are included in specific conditions.
Setting Control Logic
You can set, edit, delete and use control logic for controlling device which is
connected to DMS2.5.
1
Click [Control logic management]
£
[Setting control logic] when DMS2.5 web page
menu screen appears.
X
Apply: Indicates control logic usage status.
X
Run: Indicates If the control logic is applied and whether the operation conditions
are met.
Ex) If there is logic which says ‘If the current temperature of indoor unit is higher
than 29°C, control indoor unit as cool mode.’, 'Yes' will be displayed when the
indoor unit's current temperature is higher than 29°C. 'No' will be displayed
when the indoor unit's current temperature is lower than 29°C.
2
Click [New] when setting control logic screen appears.
X
Setting screen is composed of 4 categories.
- Name & time: Set the name and time(period, days, time) to apply of control logic.
- Factor edit: You can edit factor selection which is components of input/output.
- Input: Set the condition which makes control logic perform.
- Output: Set items to be controlled when the conditions of input are met.
Note
X
If different value is set for same control item of same address’ device, the indoor
unit follows the first control logic set among running control logics.
X
It is not available to provide the control logic management information to BMS
system.
1
2
Control Logic Management
Summary of Contents for MIM-D01AUN
Page 123: ...E 123 6 5 Click SD card restore 6 Select the check box of file to restore 7 Click OK 5 7 ...
Page 178: ...E 178 MEMO ...
Page 179: ...E 179 ...
Page 180: ...DB68 06098A 03 ...