background image

Air Source 
Heat Pump

Model Numbers

MIM-E03CN 
AE050/080/120/160RXYDEG and DGG  

Installation and Maintenance Manual
With Pre-Plumbed Cylinders

Installation Manual rework.indd   1

30/09/2019   19:24:07

 October 2019

Greenway Energy Limited 

Unit 3 Colemeadow Road 

North Moons Moat 

Redditch 

Worcestershire 

B98 9PB 

info@greenwayenergyltd.co.uk

Summary of Contents for MIM-E03CN

Page 1: ...0 080 120 160RXYDEG and DGG Installation and Maintenance Manual With Pre Plumbed Cylinders 30 09 2019 19 24 07 October 2019 Greenway Energy Limited Unit 3 Colemeadow Road North Moons Moat Redditch Wor...

Page 2: ...you are used to with a gas or oil boiler To add to this we run them in a weather compensation mode this means that the unit measures the outside temperature and adjusts the radiator temperature to su...

Page 3: ...50 C for efficiency this can be increased to operate between 53 and 60 C all the time if required As you use the water the heat pump will constantly top up the cylinder The hot water cylinder has prio...

Page 4: ...peration status display Displays the operation function settings and statuses 2 Operation On Off button LED display Turns the Air to Water Heat Pump power On Off 3 Up Down button Moves between items v...

Page 5: ...ile running check the outdoor unit for damage debris the coil needs washing we recommend you use an approved EHS heat pump cleaning chemical your distributor will stock this Instructions are given on...

Page 6: ...to the ground Dimensions Size 12 and 16 1420mm h 940mm w 330mm d 103kg Size 8 998mm h 940mm w 330mm d 75kg Size 5 798mm h 880mm w 310mm d 59kg The space around the unit is very important allow 300mm t...

Page 7: ...feeds the tundish and drains You need to install an expansion vessel on the heat pump side and the heating side of the system and one onto the cylinder The 300l cylinder needs a floor area of 700 wide...

Page 8: ...f you need Neutral use B19 Wiring Diagram Pre Plumbed Tank Sensor 15m long Don t cut this Immersion Heater Communication Cable 2 core 1mm 16Vdc Flow Switch 2m long You can extend this Power Input 16 A...

Page 9: ...ter To avoid the immersion heater cutting out before the legionella function is complete you have to set the stat in the immersion heater to 70 C minimum on a Telford cylinder set it to 5 Check the ta...

Page 10: ...ally add 2 on timers a day one at 3 00 am and one at 15 00 pm This stops nuisance tripping resets the unit after power cuts and insures the cylinder is hot 24 hours a day We don t normally set any off...

Page 11: ...educed Glycol System If you want to reduce the amount of Glycol to be used in the system you can install a plate heat exchanger The heat exchanger needs to be suitably sized if in doubt please ask Hea...

Page 12: ...sed Pump Z1 Pump HP H HW Power supply 240V 16 Amp for the 5kW 20 Amp for the 8kW 32 Amp for the 12kW 32 Amp for the 16kW F1 F2 L N Pump HP is wired Live to B8 and Neutral to B7 MAX pump power is 500W...

Page 13: ...set it to 5 Check the tank sensor The blue tank sensor MUST be installed above the immersion heater and it must be securely fixed in the tank right into the back of the pocket I would use heat paste a...

Page 14: ...ting 1 Press ok to wake the controller up 2 Press and v together for 6 seconds password shows you need to set 0202 by pressing 3 Press then twice twice twice then press OK 4 Press v 8 times to Field s...

Page 15: ...ss adjust hour to 3 pm press ok Heating Hot Water Installation Field settings for Hot Water 11 Then v to 30 DHW press ok 3011 will be highlit Domestic hot water tank press OK 12 Press v to hysteresis...

Page 16: ...ck to the normal screen Use of self test mode 1 Press OK to wake the controller up 2 Press and v together for 6 seconds password shows you need to set 0202 3 Press then twice twice twice then press OK...

Page 17: ...erature and current temperature will show To adjust the temperature press and v set it to 48 C Press ok to switch between standard eco cold water and boost only used in emergency s The heat pump will...

Page 18: ...together for 6 seconds password shows you need to set 0202 8 Press then twice twice twice then press OK 9 Press v 9 times to Self test mode press 10 You can see all the sensors on the unit at once Re...

Page 19: ...o slowly through the system With the pump running test the flow rate see page 20 and 22 If your flow rate is less than recommended you need to turn up the pumps open any valves that might be closed cl...

Page 20: ...must have no breaks or switches in it If the cable is ok it s possible one of the PCBs is at fault The hardest thing for an engineer to do is work out which end has the communication error In the midd...

Page 21: ...the heat exchanger to the heat pump 20m separation on 22mm copper for the 5kW 20 m separation on 28mm copper for the 9kW 7 5m separation on 28mm copper for the 16kW If you use a low loss header inste...

Page 22: ...ers If you are using more than one heat source heat pump boiler you MUST measure the heat produced by the heat pump and the electricity used This is essential for RHI The heat meter goes in the return...

Page 23: ...ls F1 F2 to the control box terminals F1 F2 Use 2 core flex 0 5 1mm its 16V AC It must not have any breaks in it or switches Remote controller is normally installed next to the control box out of easy...

Page 24: ...clock or a run signal from an under floor manifold B20 is permanently 240V AC The run signal goes into B22 When using multi zone heating systems on a header buffer or HEX When the stat is made it will...

Page 25: ...2 smart electric meters are used Ideally it should measure the total draw for the heat pump outdoor and indoor unit combined The outdoor unit takes most of the current so in many installations it wil...

Page 26: ...Coil Cylinder stat set at 55 C Pump HP H Z1 Z1 HW Multi Fuel 2 Heat Pumps Pump Z1 Header or Bu er Tank Heating Hot Water Heating Only Flow and returns pumped by field supplied pump Pump HP H Z1 Z1 HW...

Page 27: ...or Heat Exchanger Pump HP Heating Pools Hybrid Fast Connect Combi Boiler Board is waterproof and mounts outside behind the heat pump Boiler must be set to run below 65 C To Heating Other Systems Poss...