20
Main
menu
Sub
menu
Function
Data
bit
Factory
setting
Description
Unit
3
1
Indoor unit room temperature
1,2,3
-
Room temperature
°C
2
Indoor unit EVA IN temperature
1,2,3
-
EVA IN temperature
°C
3
Indoor unit EVA OUT temperature
1,2,3
-
EVA OUT temperature
°C
4
Indoor unit EEV step
1,2,3
-
EEV step
-
5
Indoor unit option checking (1)
Use of central control
1
-
0 – No use, 1 - Use
-
Use of drain pump
2
-
0 – No use, 1 - Use
-
Use of electric heater
3
-
0 – No use, 1 - Use
-
Use of hot water coil
4
-
0 – No use, 1 - Use
-
6
Indoor unit option checking (2)
Use of external control
1
-
0 – No use, 1 - Use
-
Use of RPM compensation
2
-
0 – No use, 1 - Use
-
Filter time
3
-
0 – 2000 hours, 1 – 1000 hours
-
Heating temperature
compensation
4
-
0-2°C, 1-5°C
-
EEV stop step in heating
5
-
0 – 1/80 steps, 1 – 80
-
4
1
Indoor Unit Option Setting 2)*
Indoor unit main address
1,2
-
main address (00H~4FH)
-
Indoor unit setup address
(manual setting main address)
3,4
-
main address (00H~4FH)
-
Indoor unit RMC address
5,6
-
main address (00H~FEH)
-
2
Indoor unit BASIC option code
1)*
-
Indoor unit option code
-
3
Indoor unit INSTALL option
1)*
-
Refer to the indoor unit
installation manual for details
-
4
Indoor unit INSTALL option(2)
1)*
-
-
5
1
AHU setting/checking
RPM setting/checking
3,4
-
0~31 steps
1 step
Humidity setting/checking
6
-
0 – 30, 1 - 40, 2 - 50
-
2
Indoor unit, AHU discharge
temperature setting/checking
Use of discharge
temperature control
1
-
0 – No use, 1 - Use
-
Cooling discharge temperature
3,4
-
8~18°C (46~64°F)
1°C
Heating discharge temperature
5,6
-
30~43°C (86~109°F)
1°C
3
Fresh Duct discharge
temperature checking
Cooling discharge temperature
1,2
-
15~25°C (59~77°F)
1°C
Heating discharge temperature
3,4
-
18~30°C (64~86°F)
1°C
6
1
ERV Plus setting/checking
Use of cold air prevention
1
-
0 – No use, 1 - Use
-
Use of humidification when
Heating thermo off
2
-
0 – No use, 1 - Use
-
Use of fan operation in Defrost
3
-
0 – No use, 1 - Use
-
Use of humidification when Heating
4
-
0 – No use, 1 - Use
-
2
ERV Plus temperature
setting/checking
Cooling
1,2
-
15~30°C (59~86°F)
1°C
Heating
3,4
-
15~30°C (59~86°F)
1°C
3
ERV Plus Auto mode
temperature setting/checking
Set temperature
1,2
-
15~30°C (59~86°F)
1°C
Set temperature difference
3,4
-
5~15°C (41~59°F)
1°C
4
Setting/checking the compensating temperature A under the
Heating EEV control for ERV Plus
1,2
-
0~10°C
1°C
Checking the compensating temperature B under the Heating
EEV control for ERV Plus
3
-
0 – Non use of
humidifier(0°C/32°F)
1 – Use humidifier(10°C/50°F)
-
5
ERV Plus fan RPM setting/
checking
Air supply RPM
1,2
-
10~27 steps
1 step
Air exhaustion RPM
3,4
-
10~27 steps
1 step
Wired Remote Controller Installation/Service Mode