12
English
Installation
Installation
• Simple BMS control is not influenced by DMS’s restrictions on operation mode, set temperature or remote controller
usage.
• If you want to set Room temperature by using Simple BMS, setting Buzzer control option as “Disuse buzzer” is
recommended.
External Controller Diagram (MIM-B14)
ÄθʀЇ̈ϩʒ̈ɇ˝θɇ͔ͱ˙ʪуϩʪθ͝ɇ̷ʀͱ͝ϩθͱ̷̷ʪθ࣭ϑ
output
GND
ĮΧʪθɇϩ̈ͱ͝ϑΧʪʀ̈ѣʀɇϩ̈ͱ͝ɇʀʀͱθʒ̈͝˝ϩͱ
AHU-KIT PBA Install option set up
WIRE
NO.
Signal
Install option
1, 2
Error check output
-
3, 4
Operation check output
SEG 15
5, 6
ON/OFF input
SEG 14
• In order for AHU-KIT to be controlled by External
control, change a digit of indoor unit installation
option, set the SEG14 as “1”. (ON / OFF control)
Simple BMS
Simple BMS setting
CAUTION
S/W
RY75 RY76 RY77
AC LAMP
CN81
CN83