Single enclosure unit
When using with the enclosure unit, design the semi-outdoor unit according to the following specifications to prevent
discharged hot air from flowing back into the inlet.
•
Air inlet(
)
Total open area of the ventilation holes: 67,000 mm or more
Minimum ventilation opening ratio (%): 50 % or more
•
Air outlet(
)
Total open area of the ventilation holes: 67,000 mm or more
Minimum ventilation opening ratio (%): 50 % or more
–
Design the locations of the enclosure unit inlet and outlet to match the locations of the semi-outdoor unit inlet and
outlet.
•
The front and back sides of the enclosure unit must be open without glass.
•
Keep clear around the product and the openings on the top and bottom to ensure good air flow.
Back
Side view
Air inlet
Air outlet
English - 19