36
AA
Testing operations
Short push
Display contents
SEG1
SEG2
SEG3
SEG4
Unit
1
Order frequency
1
Hundreds' digit
Tens' digit
Unit digit
Hz
2
Current frequency
2
Hundreds' digit
Tens' digit
Unit digit
Hz
3
The number of current indoor units
3
Hundreds' digit
Tens' digit
Unit digit
Hz
4
The sensor for outdoor air intake
4
+ / -
Tens' digit
Unit digit
°C
5
Discharge sensor
5
Hundreds' digit
Tens' digit
Unit digit
°C
6
Eva-Mid sensor
6
+ / -
Tens' digit
Unit digit
°C
7
Cond sensor
7
+ / -
Tens' digit
Unit digit
°C
8
Current
8
Tens' digit
Unit digit
The first place of decimals
°C
9
Fan RPM
9
Thousands' digit Hundreds' digit
Tens' digit
rpm
10
Target discharge temperature
A
Hundreds' digit
Tens' digit
Unit digit
°C
11
EEV
B
Hundreds' digit
Tens' digit
Unit digit
step
12
The capacity sum of indoor units
C
Tens' digit
Unit digit
The first place of decimals
kW
13
Protective control
D
0: Cooling
1: Heating
Protective control
0: No Protective control
1: Freezing
2: Non-stop defrosting
3: Over-load
4: Discharge
5: Total electric current
Frequency status
0: Normal
1: Hold
2: Down
3: Up_limit
4: Down_limit
-
14
The temperature of heat radiating plate
E
Hundreds' digit
Tens' digit
Unit digit
-
15
S/W check
F
-
-
-
-
Long push 1
Main micom version
Year (Hex)
Month (Hex)
Date (Tens' digit)
Date (Unit digit)
After short push 1
Inverter micom version
Year (Hex)
Month (Hex)
Date (Tens' digit)
Date (Unit digit)
After short push 1
E2P version
Year (Hex)
Month (Hex)
Date (Tens' digit)
Date (Unit digit)
※
Long push K4(Main micom ver.)
short push 1 more(Inv. micom ver.)
short push 1 more(E2P. ver.)
※
When snow prevention mode is in use, eco mode(standby mode)will not be functional.
7. DIP switch option
6. View Mode : When the K4 switch is pressed, you can see information about our system state as below.
On (default)
Off
switch 1
Auto address
Manual address
switch 2
Base heater operating time = 15 Min. Base heater operating time = 20 Min.
switch 3
Disable snow prevention control
Enable snow prevention control
switch 4
Enable base heater
Disable base heater