background image

Temperature/Resistance/Voltage Chart for Samsung  Refrigerators Sensors 

                      Heat Release I/M Test Mode

                                          

Press and hold the ICE TEST S/W for at least 1.5sec, the 
harvest function will start.  If the ice maker Thermistor is be-
low 0 degrees the Ice maker heater turns on for about 2 min-
utes. If the temperature exceeds 0 degrees, ice maker heater 
turns on for 30 seconds. After the ice maker heater turns on 
for 30 seconds, the heater turns off and then Ice maker har-
vest motor turns on.  The motor will rotate in right direction 
for about 3 minutes, after this, water supply valve is turned 
on, then the valve is turned off, the test mode is completed. If 
the above operation is not carried out within 6 minutes, it will 
go into a fault mode.  

           Heat Release Ice Production Explanation                           

38 minutes after the water fill is complete, the control 
board will check the temperature of the eject Thermistor,  
on the Ice Maker Head, if the Thermistor reads a tem-
perature lower than 18.5 degrees for more than 5 sec-
onds, then the ice production process is completed. The 
Ice maker will harvest if the ice bucket is not sensed as 
full.  If a Fault Mode is detected with the Ice Maker op-
eration, the Ice Maker stops working for 3 hours. Which 
means, the Ice Maker checks the operation every 3 
hours until it works properly.

 

 

                                                 FREEZER TEMPERATURE CONTROL BY THE ICE MAKER    

Interior Temperature of the freezer will be set to -14 degrees Fahrenheit until the ice bucket is full. When the ice 
bucket is full, the freezer will maintain original set temperature. Also, whenever the ice is used, the freezer will 
again set to -14 degrees Fahrenheit. Selecting "Ice Off” will allow the freezer to be controlled by the set tem-
perature. If water is not hooked up, the freezer will always be at –14 unless “Ice Off” is selected.

 

Temp. (

) Volts 

 

 Temp. (

) Volts 

 

 

Temp. (

) Volts 

 

 

Temp. (

) Volts 

-29.2°F 64227 4.326  

  1.4°F 28021 

3.685 

 

 

32.0°F 13290 2.853  

 62.6°F 6771 2.019 

-27.4°F 61012 4.296  

  3.2°F 26760 3.64 

 

 

33.8°F 12749 2.802  

 64.4°F 6521 1.974 

-25.6°F 57977 4.264  

  5.0°F 25562 

3.594 

 

 

35.6 °F  12233  2.751     66.2°F 6281 1.929 

-23.8°F 55112 4.232  

  6.8°F 24425 

3.548 

 

 

37.4 °F  11741 

2.7 

   68.0°F 6052 1.885 

-22.0°F 52406 4.199  

  8.6°F 23345 

3.501 

 

 

39.2 °F  11271  2.649     69.8°F 5832 1.842 

-20.2°F 49848 4.165  

 10.4°F 22320 3.453 

 

 

41.0°F 10823 2.599  

 71.6°F 5621 1.799 

-18.4°F 47431 4.129  

 12.2°F 21345 3.405 

 

 

42.8°F 10395 2.548  

 75.2°F 5225 1.716 

-16.6°F 45146 4.093  

 14.0°F 20418 3.356 

 

 

44.6°F 9986 2.498  

 77.0°F 5000 1.675 

-14.8°F 42984 4.056  

 15.8°F 19537 3.307 

 

 

46.4°F 9596 2.449  

 78.8°F 4861 1.636 

-13.0°F 40938 4.018  

 17.6°F 18698 3.258 

 

 

48.2°F 9223 2.399  

 80.6°F 4690 1.596 

-11.2°F 39002  3.98  

 19.4°F 17901 3.208 

 

 

50.0°F 8867  2.35  

 86.0°F 4218 1.483 

-9.4°F 37169 3.94  

 21.2°F 17142 3.158 

 

 

51.8°F 8526 2.301  

 87.8°F 4072 1.447 

-7.6°F 35433 3.899 

 

 23.0°F 16419 3.107 

 

 

53.6°F 8200 2.253  

 89.6°F 3933 1.412 

-5.8°F 33788 3.858 

 

 24.8°F 15731 3.057 

 

 

55.4°F 7888 2.205  

 91.4°F 3799 1.377 

-4.0°F 32230 3.816 

 

 26.6°F 15076 3.006 

 

 

57.2°F 7590 2.158  

 95.0°F 3547 1.309 

-2.2°F 30752 3.773 

 

 28.4°F 14452 2.955 

 

 

59.0°F 7305 2.111  

 96.8°F 3428 1.277 

-0.4°F 29350 3.729 

  

30.2°F 13857 2.904 

 

 

60.8°F 7032 2.064  

 100.4°F 3204 1.213 

Heat Release Ice Makers 

 

DC FAN MOTORS

 

Brushless DC Fan motors are used to save energy. The fans operate at two speeds. Fan speed information is read by 
the Main PCB. If the fan speed exceeds 600 RPM or the speed is too slow, or stopped the fan drive circuit is disabled,  
After 10 seconds the circuit tries again with 3 seconds of DC voltage. If the fan continues this activity for 5 cycles, 10 
seconds off 3 seconds on, the fan drive circuit is disabled for 10 minutes. 

TO TEST THE FAN CIRCUIT VOLTAGE. 

Power off and back on to check the DC voltage to the motor, wait from 10 to 60 seconds for the fan voltage to kick in, 
and then check fan voltage, the average reading is 9 VDC.  If you get 3 seconds of voltage every 10 seconds for the 5 
fan power up cycles, then the Main PCB is good. 

NOTE: 

You may need to put unit in FORCED FREEZE mode to activate the fans/compressor. 

If the fan blade is blocked by ice, then defrost and check the motor again, after removing power from the unit. 
If the evaporator is ice blocked and thus blocking the air flow, the fan will over RPM and will be stopped. Remove ice 
and check the motor again. If everything is clear around the fan blade then the motor would be at fault. Continuous fan 
errors will be displayed on the front panel display. 

PLEASE NOTE: 

The door switches control the evaporator fan mo-

tors. Have them closed to test the motors. Delay time 10 – 60 seconds. 

2

 

 

2

Reviews: