42
Indoor unit setting
Power and communication cable connectiona
When MAIN address is set as "12".
For Example
When RMC address is set as "12".
For Example
SW03
SW04
SW01
SW02
SW03
SW04
SW05
SW06
SW07
SW08
SW09
The designs and shape are subject to
change according to the model.
1. Before installing the indoor unit, assign an address to the indoor unit according to the air conditioning system plan.
2. The address of the indoor unit is assigned by adjusting MAIN(SW01, SW02) and RMC(SW03, SW04) rotary switches.
Setting Main Address
The MAIN address is for communication between the indoor unit and the outdoor unit.
Therefore, you must set it to operate the product properly.
You can set the MAIN address from ‘00’ to ‘99’ by mixing SW01 and SW02.
The MAIN address from ‘00’ to ‘99’ should differ from each other.
Check the indoor unit address on the plan that you are to install and set the address according to
the plan.
Setting RMC Address
The SW03, SW04 RMC switch is the address setting switch for controlling the indoor unit with the
centralized controller.
You must set the SW03,SW04 and K2 switch when using the centralized controller.
You don't have to set the SW03 and SW04 RMC switch when not suing the centralized controller.
• You may not need to set main address if you selected Auto Address Setting from the outdoor unit: see details
on the outdoor unit installation manual.