42
|
SAMSUNG
INSTALLATION
5
5-4. Placing the Indoor Unit in Position
●
Once you have checked that there are no leaks in the system, you can insulate the piping, hose and cables and place
the indoor unit on the installation plate.
1. To avoid condensation problems, place heat-resistant polyethylene foam
separately around each refrigerant pipe in the lower part of the indoor unit.
2. Wind insulating tape around the pipe, assembly cable and drain hose.
3. Place the resulting bundle carefully in the lower part of the indoor unit,
making sure that it does not jut out from the rear of the indoor unit.
4. Hook the indoor unit up to the installation plate and move the unit to the
right and left until you are sure that it is securely to place in.
5. Finish wrapping insulating tape around the rest of the piping leading
to the outdoor unit.
6. Using clamps (optionally supplied), attach the piping to the wall
wherever possible.
Placing the Indoor Unit in Position
Installation
plate
DB98_16444A(1)_1 2/9/04 10:04 AM Page 42
Summary of Contents for SH07APG
Page 2: ...Model Line Up 1 1 Model Identification 1 2 Model Line Up 1 ...
Page 3: ......
Page 8: ...Specifications 2 1 Table 2 ...
Page 9: ......
Page 12: ...Outline Dimension 3 1 Indoor Unit 3 2 Outdoor Unit 3 ...
Page 13: ......
Page 17: ...MEMO 16 SAMSUNG ...
Page 18: ...SAMSUNG 17 Performance Data 4 1 Performance Data 4 ...
Page 19: ...18 SAMSUNG ...
Page 27: ...MEMO 26 SAMSUNG ...
Page 29: ......
Page 47: ......
Page 64: ...Diagram 7 1 Refrigerating Cycle Block Diagram 7 2 Circuit Diagram 7 3 Circuit Description 7 ...
Page 65: ......
Page 76: ...Troubleshooting 8 1 Troubleshooting for Non Inverter 8 2 Set up the Model Option 8 ...
Page 77: ......
Page 92: ...MEMO SAMSUNG 91 ...
Page 93: ...MEMO 92 SAMSUNG ...
Page 94: ...ELECTRONICS Samsung Electronics Co Ltd Feb 2004 Printed in Korea Code No DB98 16444A 1 ...