Details for Operation Property
(cont.)
6-2-12. Low Temp Release
●
AT COOLING MODE
◆
If the temperature of indoor heat exchanger is below -1°C for over 6 minutes, the outdoor fan turns off.
◆
If the temperature of indoor heat exchanger increase over 5°C during the first protection function, the first freezing protection
function is released and the outdoor fan turns on.
◆
If the temperature of indoor heat exchanger increase over 0°C during 6 minutes counting, 6 minutes counter is cleared.
◆
If the temperature of indoor heat exchanger maintains for a minute at -4°C during the 6 minutes counting, switch off the
compressor.
◆
If the compressor is off by Low Temp. Release, 5 minutes release is impossible.
◆
Operating Pattern
Indoor Heat exchanger Temp.(˚C)
5[˚C]
0[˚C]
-1[˚C]
6min
COUNT
ON
COUNT
ON
COUNT
OFF
6min
6min Low
temp.
release
ON
Low temp.
release
OFF
6min
3sec
2sec
ON
ON
OFF
ON
ON
OFF
Setting Fan speed
Setting Fan speed
"LL"
COMP_or
Outdoor FAN
Indoor FAN
✳
LL = Low FAN speed – 35rpm
DB98_16444A(1)_1 2/9/04 10:04 AM Page 58
Summary of Contents for SH07APG
Page 2: ...Model Line Up 1 1 Model Identification 1 2 Model Line Up 1 ...
Page 3: ......
Page 8: ...Specifications 2 1 Table 2 ...
Page 9: ......
Page 12: ...Outline Dimension 3 1 Indoor Unit 3 2 Outdoor Unit 3 ...
Page 13: ......
Page 17: ...MEMO 16 SAMSUNG ...
Page 18: ...SAMSUNG 17 Performance Data 4 1 Performance Data 4 ...
Page 19: ...18 SAMSUNG ...
Page 27: ...MEMO 26 SAMSUNG ...
Page 29: ......
Page 47: ......
Page 64: ...Diagram 7 1 Refrigerating Cycle Block Diagram 7 2 Circuit Diagram 7 3 Circuit Description 7 ...
Page 65: ......
Page 76: ...Troubleshooting 8 1 Troubleshooting for Non Inverter 8 2 Set up the Model Option 8 ...
Page 77: ......
Page 92: ...MEMO SAMSUNG 91 ...
Page 93: ...MEMO 92 SAMSUNG ...
Page 94: ...ELECTRONICS Samsung Electronics Co Ltd Feb 2004 Printed in Korea Code No DB98 16444A 1 ...