Samsung Electronics
21
3. Disassembly and Reassembly
3-1 Necessary Tools
Refrigerant pipe installation
Refrigerant pipe work
∙
The length of refrigerant pipe should be as short as possible and the height difference between an indoor and outdoor unit
should be minimized.
∙
Piping work must be done within allowable piping length, height difference, and the allowable length after branching.
∙
The pressure of the R-410A is high. Use only certified refrigerant pipe and follow the installation method.
∙
After installing the pipes, calculate the total length of the pipe to check if additional refrigerant is needed.
When you need to charge the additional refrigerant, make sure to use R-410A refrigerant.
∙
Use clean refrigerant pipe and there shouldn’t be any harmful ion, oxide, dust, iron content or moisture inside pipe.
∙
Use tools and accessories that fit on R-410A only.
Tool
Installation process/purpose
Compatibility with conventional tool
Pipe cutter
Refrigerant pipe
installation
Pipe cutting
Compatible
Flaring tool
Pipe flaring
Refrigerant machine oil
Apply refrigerant
oil on flared part
Exclusive ether oil, ester oil, alkali benzene oil or synthetic oil
Torque wrench
Connect flare nut
with pipe
Compatible
Pipe bender
Pipe bending
Nitrogen gas
Air tightness test
Prevent oxidation
within the pipe
Welder
Pipe welding
Manifold gage
Air tightness test ~
additional
refrigerant charging
Vacuuming,
charging
refrigerant
and checking
operation
Need exclusive one to prevent mixture of R-22 refrigerant oil use
and also the measurement is not available due to high pressure
Refrigerant charging hose
Need exclusive one since there is risk of refrigerant leakage or inflow
of impurities
Vacuum pump
Pipe drying
Compatible (Use products which contain the check valve to prevent
the oil from flowing backward into the outdoor unit.)
Use the one that can be vacuumed up to -100.7kpa(5Torr).
Scale for refrigerant charg-
ing
Refrigerant charging
Compatible
Gas leak detector
Gas leak test
Need exclusive one. (Ones used for R-134a is compatible)
Flare nut
Must use the flare nut equipped with the product.
Refrigerant leakage may occur when the conventional flare nut for R-22 is used.