Samsung Electronics
12-2-4 Total current Trip error
1. Checklist :
1) Is the input power voltage proper?
2) Is the refrigerant charged properly?
3) Does the compressor rotate normally? (Reverse rotation, Locking etc.)
4) Dose the outdoor fan operate normally? (Fan propeller loss, Motor error etc.)
5) Is the installation condition of outdoor unit good? (Piping, Space etc.)
6) Is there no ventilation obstruction at the surrounding of outdoor? (Outdoor unit cover, Fan front obstruction etc.)
2. Troubleshooting procedure
No
Exchange the PCB.
No
Exchange the PCB.
No
Exchange the compressor.
No
Reinstall and remove the obstruction.
Yes
Yes
Yes
Yes
Is the installation of outdoor unit good?
Dose the compressor rotate normally?
Is the assembly of R418, R413, IC41, C437
and the peripheral part good?
Pull out the power cord and exchange
the PCB from the case after 30 seconds.
Is the assembly of Micom and
peripheral circuit part good?
Check again after assembly of PCB.
Troubleshooting
12-5
25888A(1)_1.indd 34
2006-04-14 ソタネト 2:26:12
Summary of Contents for UH035EAV Series
Page 46: ...MEMO Samsung Electronics 4 27 ...
Page 57: ...Samsung Electronics 5 11 5 3 Ass y Control Out UH035EAV DB93 03453A ...
Page 59: ...Samsung Electronics Ass y Control Out cont UH052EAV DB93 03665D UH070EAV DB93 03665E 5 13 ...
Page 106: ...Samsung Electronics MEMO 8 5 ...
Page 111: ...9 2 Refrigerating Cycle Diagram 9 5 Samsung Electronics EH035EAV UH035EAV ...
Page 112: ...Samsung Electronics EH052EAV UH052EAV EH070EAV UH070EAV Circuit Descriptions 9 6 ...
Page 164: ...Samsung Electronics 14 10 MEMO ...
Page 165: ...Samsung Electronics MEMO 14 11 ...