Samsung Electronics
Troubleshooting
12-3 Sequence for trouble diagnosis
Reoperation
after connect to
connector PCB
Yes
Outdoor unit thermistor
is defective(replace)
No
PCB and sensor are normal.
To perform the test
operation by use of K2
12-3-1 Outdoor temp. sensor(OPEN/SHORT)
Outdoor unit display
Indoor unit display
How to determine
Reason of error
(
Outdoor temp. sensor OPEN/SHORT error
)
(Operation) (Timer) (Airflow) (Filter)
Disconnection and short of outdoor temp. sensor
Disconnection or leak of applied sensor
Yes
No
Yes
Check the out temp.
sensor is normal or not by use of
out data display part
Check the temp. data is
normal or not after pressing K4 3 times.
At this time, is occurred the difference
between the out temp. and data?
Reoperation after PCB replacement
Does the out temperature
sensor connected to PCB?
(CN41)
At this time, Is largely
deviate the resistance value from side
table value?
Temp.
(˚C)
70
60
50
40
30
20
10
0
-10
Resistance
(kΩ)
2.2
3.0
4.2
5.8
8.3
12.1
18.0
27.3
43.0
Measure the resistance value
between two terminals after
separating the out temp. sensor
connector from PCB
No
12-6
Summary of Contents for UH052EAMC
Page 34: ...Samsung Electronics 5 2 Panel 5 4 ...
Page 44: ...Samsung Electronics 5 4 Ass y Control In CH140EAMC DB93 04137A 5 14 ...
Page 46: ...Samsung Electronics CH105EAMC DB93 04376A Exploded Views and Parts List 5 16 ...
Page 48: ...Samsung Electronics CH052 070 094EAMC DB93 05254A Exploded Views and Parts List 5 18 ...
Page 54: ...Samsung Electronics UH052 070EAMC DB93 04731B DB98 04731A Exploded Views and Parts List 5 24 ...
Page 76: ...Samsung Electronics 7 8 MEMO ...
Page 89: ...Samsung Electronics 10 8 MEMO ...
Page 125: ...Samsung Electronics 14 10 MEMO ...