Connecting the cable
Wiring Diagram of Power Cable
ELB
MCCB
MCCB
When using ELB for 1 phase
Power Supply
Electrical component box
Indoor Unit
Main power cable
Connection cord
Communication
cable
Cable
clamp
Outdoor unit
You should connect the power cable into the power cable terminal and
fasten it with a clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser.
If the unbalanced power is exceeded over 4% of supply rating,
the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the
power cable and the connection cord of the indoor and outdoor units in the
iron pipe.
Ensure that main supply connection is made through a switch that disconnects
all poles, with contact gap of a least
0.118 inch(3 mm)
.
Must keep the cable in a protection tube.
Keep distances of
1.968 inch(50 mm)
or more between power cable and com-
munication cable.
CAUTION