ENGLISH
E-
13
Connecting the cable (Continued)
When using an ELB for 3 phase 4 wires (UH140/105GAMC
)
Power Supply
Electrical component box
Indoor Unit
3 Phase
4 Wires
MCCB
ELB
MCCB
Communication
Cable
Connection cord
3 Phase 4 Wires
Power Cable
(AC 380V)
Cable
clamp
Main PCB
A
B
You should connect the power cable into the power cable terminal and fasten it
with clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser. If the
unbalanced power is exceeded over 4% of supply rating, the indoor unit is protect
ed, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the power
cable and the connection core of the indoor and outdoor units in the iron pipe.
Connet the power cable to the auxiliary circuit breaker.
An all pole disconnection from the power supply must be incorporated in the fi xed
wiring(>=3mm).
When connecting cables, make the cable pass through the cable tube as shown at
the fi gure.
Must keep the cable in a protection tube.
Keep distances of 50mm or more between power cable and communication
cable.
Communation cable
Connection cord
Power cable
Liquid refrigerant pipe
Gas refrigerant pipe
Cable tube
CAUTION