45
10. Installation
When the water pipe passes through back of the product
(Unit : mm)
<Top view>
Service space
Front side
C
Space for
installing water
pipe
300
Outdoor
unit
350 A
300
B
500
<Front view>
Anti-vibration pad
1000
100
100
Module or continuous installation
<Top view>
(Unit : mm)
Service space
Front side
C
20
Outdoor
unit
350
A
100
B
300
350
A
100
Service space
Front side
Outdoor
unit
Model name of outdoor unit
A
B
C
AM080/100/120MXWA∗∗
770
545
600
AM200MXWA∗∗ / AM300KXWA∗∗
1100
545
600
•
If the outdoor unit is needed to be installed close to the walls unavoidably, prevent the vibration from
being transferred to the walls with cushioning materials etc.
CAUTION