57
10. Installation
Water pipe installation
It is recommended to use closed circuit cooling tower. If open cooling tower is applied, use intermediate heat exchanger and
make sure that supplied heat source water system is closed circuit.
Water pipe installation
T
T
Water pipe IN
<Pipe connection part>
He
at e
xch
anger
50 or more
Water pipe
Insulator
80 mm or
mor
e
Finishing tape
Anti-vibration pad
Support to prevent
loading on the pipe
Strainer (must
be purchased
separately)
Protection tube
Ball valve
2Way solenoid valve
Flange
Water pipe
<Water pipe diagram>
<Connecting pipe before test operation>
Water pipe
connection
hose
Pipe for cleaning
Flexible
joint (absorb
vibration)
Flow switch
(Mandatory
connection)
※
From above illustration, flow switch (mandatory) and 2way solenoid valve (optional) must be at least equivalent
to the specification recommended by our company and they should be installed horizontally.
When water pipe circuit freezes, it will cause damage to the plate type heat exchanger and therefore
preventive measure must be taken according to the situation.
•
Drain remaining water in the water pipe when it will not be used for long period of time
•
Constantly operate the water pump to circulate the water within the water pipe
•
Install self-regulating heat cable on the water pipes
CAUTION
※
Design condition
Type
Circulating
water
Operation
Inlet water temperature
Remarks
Main usage range
Usage range limit
Note 3)
Heat source
water
Water loop
Cooling
20 ~ 35 °C
10 ~ 45 °C
Refer to
'Cooling water
management'
on page 96
Heating
Ground heat
source
Note1)
Ground loop
Cooling
15 ~ 35 °C
10 ~ 45 °C
Heating
5 ~ 25 °C
-5 ~ 45 °C (-10 ~ 45 °C)
Note 2)
Note 1): Anti-freeze must be used when temperature of water inlet for heating is below 10°C or ground heat source is used. Maintain
appropriate concentration level of anti-freeze according to temperature of water inlet.
Note 2): Strict management of anti-freeze concentration level is required. Consult Samsung before application.
Note 3): When inlet water temperature is outside of limit, consult Samsung before application.