PAGE 27of 46 HG-1-1701 GAS-FIRED HEATER   

LAST UPDATED: JAN-25-2022 © SAMUEL JACKSON, INCORPORATED 2011 ALL RIGHTS RESERVED

 

 

GAS LOW PRESSURE -- 

The blower is on for this step. The SSOV1 and SSOV2 are 

now used to test for presence of gas, adjust its pressure, test for valve leakage.  The final 
pressure should be between 2.5 and 3 PSI when the heater is operating.   
 
With  the  gas  cavity  charged,  leave  the  valves  closed  several  minutes  to  see  that  the 
pressure  does  not  leak  off.    This  tells  us  that  the  Safety  Shutoff  Valve  SSOV2,  is  not 
leaking. Evacuate the gas cavity. Leave the valves closed several minutes to see that the 
pressure does not build up.  This tells us that the upstream valve, SSOV1, is not leaking.  
The  operating  program  will  perform  similar  tests  every  time  the  heater  is  shut  down.  
This is one reason electrical power must be supplied to the heater continuously, or at least 
for 10 minutes after each shutdown.  
 
In rare cases, the screen on the inlet to the SSOV block may become clogged with debris 
from the gas supply. Evidence of this will be gas low pressure errors and a loss of heat 
output while the pressure shown on Gas Pressure Gauge 2 (GPG2) is normal of about 3 
PSI. The GPG1 pressure tap is upstream of the screen. To clean the screen, it is necessary 
to remove the valve block from the flanged inlet and outlet pipe fittings.  
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

IGT TRANSFORMER -- 

The blower will turn on when this test is entered, and it must 

run 20 seconds to purge the duct system with air before this test can proceed. Turn on the 
Ignition Transformer IGT. If the gin is quiet, you can hear the spark.  If there is difficulty, 
check the spark plug electrode gap at 1/16 to 1/8" (1.5 to 3 mm). Hold the IGT on for two 
seconds while observing the flame light on the local panel LP.  If the Flame Signal turns 
on, it means that there is electrical interference between the spark plug wire and the flame 
electrode  wire.    They  should  be  run  to  the  burner  in  separate  conduits  to  avoid  such 
interference. Since the operating program makes a similar test before each ignition, the 
burner will not operate until this problem is corrected. INTERFERENCE will flash on the 
display if electrical interference occurs. 
 

Try the Burner to see if it lights – 

Try to start from the Home screen.   

 

If flame fails during startup, Fuel Valve at Ignition position can be increased and try to 

light again.  

 

 

 

Screen on inlet to SSOV block 

GPG2 

SSOV 
block 

Summary of Contents for HG-1-1701

Page 1: ...PAGE 1of 3 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED 1 HG 1 1701 1 Million Btu Hr Gas Fired Heater Service and Operation Guide...

Page 2: ...PAGE 2of 3 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED 2 HG 1 1701 GAS FIRED HEATER...

Page 3: ...TEST 15 VIEW OPERATION DETAILS AND STATISTICS 16 HOW DO I SET THE TEMPERATURE 17 WHERE DO I INSTALL THE AIR TEMPERATURE THERMOCOUPLE 17 OPTIONAL MOISTURE MIRROR 3X 4X AND SPECTRUM 18 FOR REMOTE CONTTR...

Page 4: ......

Page 5: ...more detailed information will be shipped to you under separate cover specifically for your system IS STARTUP ASSISTANCE PROVIDED Depending upon your location a startup and inspection service may be...

Page 6: ...e us a call and we will gladly send you the latest product information DANGER Please read and understand all the warnings below before operating or maintaining a Samuel Jackson product If you do not u...

Page 7: ...ly Samuel Jackson approved parts Do not work on any Samuel Jackson product without first following OSHA Lockout Tagout procedures Confirmation by a licensed electrician that there is no electricity pr...

Page 8: ...r to keep condensation and buildup to a minimum is a necessity The HG 1 1701 1 million BTU hr Gas Fired Heater was developed to meet this need It comes complete with blower fan motor to make installat...

Page 9: ...reen shows Ready near the bottom the heater is ready to run Push the flame button to start the heater The heater s blower will start and various operations will be displayed as the self checks and ign...

Page 10: ...m with one of these devices it alerts the operator on the display with a description of the problem These diagnostics are performed every time the heater is started and continue during operation until...

Page 11: ...flame appear in the heater body image to indicate that the flame rod is detecting a flame The timer will appear at the top of the screen and the thermocouple temperature will increase toward setpoint...

Page 12: ...unning Identification is where the heater can be named and heater number changed Fuel Limits is where fuel pressure and valve limits can be set Temp Limits is where maximum operating temperature along...

Page 13: ...a flame than to maintain it after ignition Default setting is 15 Min Fuel Valve During Run Some gas must flow through the main butterfly valve even at low fire to maintain a flame This minimum gas val...

Page 14: ...N MAX The minimum maximum Before Mix air temperature set point SP the user can adjust the control to is set in this step The factory default is 350 degrees F The adjustable range is from highest minim...

Page 15: ...best operation of the heater in most situations If the tuning has been corrupted or changed and a return to the original factory setting is desired set AM RESET to 20 00 set BM RESET to 10 00 PID SET...

Page 16: ...CKSON INCORPORATED 2011 ALL RIGHTS RESERVED DATE TIME SETTINGS Before using for the first time the Date Time Time Zone and Daylight Savings Time should be set SET USER PASSWORD This is used to changed...

Page 17: ...omatically The heater will alternate between the two tests after each normal shut down The test takes about 10 minutes to perform and the status of the tests is shown on the touch screen Leak Test 1 c...

Page 18: ...lves closed several minutes to see that the pressure does not build up This tells us that the upstream valve SSOV1 is not leaking Repeating the above steps to charge the cavity but energizing SSOV2 wi...

Page 19: ...n wire and the flame relay wire are electrically isolated from each other Note that the Fan and Air interlocks are indicated at the top of the page The fan must run to evacuate any gas from the heater...

Page 20: ...ton will open the Operation Detail screen as seen below Diagnostics is the same as the Test Setup screen and will help in troubleshooting Error History shows the Error Log and Version shows informatio...

Page 21: ...nding upon the minimum and maximum set point settings that have been made in the Setup Screen under Temp Limits WHERE DO I INSTALL THE AIR TEMPERATURE THERMOCOUPLE A thermocouple with blue paint on th...

Page 22: ...trol normally at the ginner s console of the heater via a CAT5 6 Ethernet connection The START STOP operations temperature settings and information like run times are displayed on the Mirror s color t...

Page 23: ...DGED CODE ERR ALM BRIEF DESCRIPTION 422 A LOW FIRE SWTICH STAYS ON 423 A LOW FIRE SWITCH NEVER ON 432 A MOMENTARY LOW AIR FLOW 433 E LOW AIR FLOW 435 E UPSTEAM GAS LEAK DETECTED CHECK SSOV1 FOR LEAKS...

Page 24: ...FUEL INLET 624 A NO SIGNAL GAS PRESSURE 1 631 A NO SIGNAL AIR FLOW 1 633 A NO SIGNAL AMBIENT TEMP 634 A NO SIGNAL BEFORE MIX TEMPERATURE 1 635 A NO SIGNAL BEFORE MIX TEMPERATURE 2 636 A NO SIGNAL AFT...

Page 25: ...to open Alarm 423 LOW FIRE SWITCH NEVER ON Did the fuel mod motor fail to close ALARM 432 MOMENTARY LOW AIR FLOW This ERROR is an indication that a choke of the air flow is occurring It is displayed w...

Page 26: ...oof of closure switch POC Replace SSOV1 valve actuator and or its proof of closure switch See FUEL SYSTEM section of TESTS for testing of the valves ERROR 446 EXCESSIVE FLAME FAILURES During ignition...

Page 27: ...e runs to the thermocouple location and cool ambient temperatures ALARM 611 BEFORE MIX THERMOCOUPLE 2 REVERSED Verify wiring in thermocouple per diagram This can also be caused by long pipe runs to th...

Page 28: ...ue thermocouple 1 Replace AM thermocouple ALARM 637 NO SIGNAL AFTER MIX TEMPERATURE 2 Check wiring to AM blue thermocouple 2 Replace AM thermocouple ERROR 640 HIGH GAS PRESSURE Reset high gas pressure...

Page 29: ...ir by closing off the gas supply valve before the Gas Pressure Regulator GPR and having the main gas supply on Open the pipe cap on the end of the short pipe debris trap nipple under the regulator and...

Page 30: ...are made on Control Voltage Transformer CT referring to the ELECTRICAL SCHEMATIC Drawing No CA17011C shown in this manual Call the factory for assistance Gas Train Status Observe the state of the gas...

Page 31: ...put while the pressure shown on Gas Pressure Gauge 2 GPG2 is normal of about 3 PSI The GPG1 pressure tap is upstream of the screen To clean the screen it is necessary to remove the valve block from th...

Page 32: ...adjust the orifice alignment remove the contoured disk from the burner body by removing the 3 8 inch stainless steel cap screw Rotate the orifice disk so that one of the slots is pointed directly at...

Page 33: ...EAST 10 FEET FROM BURNER OUTLET 1 2 CONDUIT WITH 1 PAIR SHIELDED CABLE DO NOT RUN WITH AC VOLTAGE WIRES OKAY TO RUN WITH OTHER THERMOCOUPLE OR DC VOLTAGE WIRES SEE THERMOCOUPLE WIRING SECTION FOR MORE...

Page 34: ...terminal blocks Terminate the shield only on the electrical panel end Do not use Type J thermocouple wire for hookup Never run the shielded sensor wires with the power wiring including 120 VAC control...

Page 35: ...PAGE 31of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED WIRING DIAGRAMS...

Page 36: ...PAGE 32of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...

Page 37: ...PAGE 33of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...

Page 38: ...he building without extreme dilution The terminating end shall be protected against water entry and bug screened Vent pipe shall be of adequate size so as to not lengthen response time 3 3 4 3 3 Vent...

Page 39: ...PAGE 35of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...

Page 40: ...PAGE 36of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED...

Page 41: ...AGE 37of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED GVM GPG3 GPG2 POC GPT2 SSOV PLC PS FLR AFT CB MC MOL CA17013 CT SW Heater Component...

Page 42: ...PAGE 38of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED CA17013 TS GFLT GPT1 GPG1 GPR...

Page 43: ...PAGE 39of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED CA17013 TS GFLT GPT1 GPG1 GPR...

Page 44: ...PAGE 40of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED CA17013 IGT AMB IGP FE...

Page 45: ...BURNER 12399A CA390 FLR FLAME RELAY UPPER CABINET 26540 LFS1 GFLT GAS FILTER 24679 6 BAR 1 OUTSIDE CABINET GPG1 GAS PRESSURE GAUGE 0 60 PSI 25666 BCM DIAPHRAGM OUTSIDE CABINET GPG2 GAS PRESSURE GAUGE...

Page 46: ...616 LRD10 UPPER CABINET PLC PROGRAMMABLE LOGIC CONTROLLER UPPER CABINET 25678 COMPRISED OF 25686 25679 25680 25681 25682 POC PROOF OF CLOSURE SWITCH LOWER CABINET 21328 D224253 CPI 400 PS POWER SUPPLY...

Page 47: ...PAGE 43of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED BURNER HEAD ASSEMBLY...

Page 48: ...T DIMENSIONS IN INCHES CENTIMETERS 4 SPACES 5 00 12 7 20 00 50 8 2 00 5 1 FLANGE 57 50 146 1 48 75 123 8 87 66 222 7 CONNECT 3 PHASE POWER HERE GAS INLET 1 INCH PIPE 1 00 2 5 17 88 45 4 SQUARE INSIDE...

Page 49: ...PAGE 45of 46 HG 1 1701 GAS FIRED HEATER LAST UPDATED JAN 25 2022 SAMUEL JACKSON INCORPORATED 2011 ALL RIGHTS RESERVED WARRANTY...

Page 50: ...ations to meet the particular requirements Implementation of alternative safety devices may incur additional charges No warranty of compliance with a particular standard is made in the absence of spec...