6. LED INDICATIONS
LED NAME
STATUS
MEANING
Power
ON
Device is ON
LED
ON
Device is waiting to enter
configuration mode
TX
ON
Device is Transmitting Data
RX
ON
Device is Receiving Data
7. MEMORY MAP in SC15L APS
1. DI Data: a) Function Code
– 02: INPUT STATUS
2. AI Data: a) Function Code
– 03: HOLDING RESISTER
3. DO Data:
a) To read DO data use Function Code
– 01: COIL STATUS
b) To write on single DO use Function Code
– 05: FORCE SINGLE COIL
SC15L
Device
ID
Memory Length
DI (FC : 02)
AI (FC : 03)
DO (FC : 01)
1
0-29 (30 Bytes)
0-7 (8 Bytes)
8-23 (16 Bytes)
24-27 (4
Bytes)
2
30-59 (30 Bytes)
30-37 (8 Bytes)
38-53 (16
Bytes)
54-57 (4
Bytes)
3
60-89 (30 Bytes)
60-67 (8 Bytes)
68-83 (16
Bytes)
84-87 (4
Bytes)
4
90-119 (30 Bytes)
90-97 (8 Bytes)
98-113 (16
Bytes)
114-117 (4
Bytes)
5
120-149 (30 Bytes) 120-127 (8
Bytes)
128-143 (16
Bytes)
144-147 (4
Bytes)
6
150-179 (30 Bytes) 150-157(8
Bytes)
158-173(16
Bytes)
174-177(4
Bytes)
7
180-209(30 Bytes)
180-187(8
Bytes)
188-203(16
Bytes)
204-207(4
Bytes)
8
210-239(30 Bytes)
210-217(8
Bytes)
218-233(16
Bytes)
234-237(4
Bytes)
9
240-269(30 Bytes)
240-247(8
Bytes)
248-263(16
Bytes)
264-267(4
Bytes)
10
270-299(30 Bytes)
270-277(8
Bytes)
278-293(16
Bytes)
294-297(4
Bytes)
Starting Address Calculation Method
DI: (SC15L Device ID-1)*30