Shipping and Handling
8
S&C Instruction Sheet 761-515
6.
Erection Drawing:
A detailed erection drawing (ED) for the Alduti-Rupter Switch will
be found in a water-resistant envelope shipped with the switch. If a standard mounting
arrangement is to be used, this erection drawing is a printed sheet. This same sheet is
also furnished when a standard minor modification of a standard mounting arrangement
is used. A copy of RD-1329 (Standard Minor Modifications, Rotating Operating
Mechanisms) is included. A custom erection drawing will be provided for special
mounting arrangements. Contact your nearest S&C Sales Office for details.
7.
Power Operation:
If suffix “-S8,” or “-S9” is specified, S&C Instruction Sheets 769-500
and 769-501, “S&C Switch Operators—Type AS-1A,” are included with the switch
operator shipment. Instruction Sheets 769-500 and 769-501 cover installation, operation,
and adjustment of the switch operator and should be used in conjunction with this
instruction sheet where applicable. If suffix “-S16” is specified, associated S&C
instruction sheets for the 6801M Automatic Switch Operator are included with the
switch operator shipment and should be used in conjunction with this instruction sheet
where applicable. Not all mounting arrangements are suitable for power operation.
Consult your nearest S&C Sales Office for details.
8.
Fused Interrupter Switch.
Although the interrupter switch photos shown in this
instruction sheet are not fused, the installation procedure is identical for a fused
interrupter switch.
Handling
The crate the switch pole-units is packed in is designed to be moved and lifted using a lift
truck. Raised slots at the bottom of the crate are provided for a lift truck’s forks.
NOTICE
To minimize time-consuming final adjustments after installation, make sure the switch
poles are in their fully
Closed
position and their toggle mechanisms are against their
closed stops during installation of both the interphase and vertical operating-pipe sections .
Switch blades can be tied to their jaw-contact members, and the toggle mechanisms can
be tied to their stops .
WARNING
DO NOT lift the switch pole-units by rigging on the “live parts” or subject these parts to
undue stress from slings or fall lines . Lifting the pole-units by the live parts will damage the
switch . Rough handling may cause damage to the blades, contacts, and/or interrupters .
Failure to lift the pole-units properly can result in switch damage, causing improper
operation, arcing, or electrical shock .