24 S&C Instruction Sheet 1023-550
The
Chronological Log
screen shows a log of various troubleshooting-related events.
This information may help identify the cause of problems. See Figure 6. To display the
Chronological Log
screen from the
Data
menu, select the Event/Data Logs entry, and
double-click on the Event_Logs entry. Click on the Chronological Log entry. If desired,
enter a date range for the data you want to view. Then click on the
OK
button. The
IntelliLink software automatically opens a browser window to display the data.
Chronological Log
Figure 6. The Chronological Log screen.
The log holds 31 events. When the log is full, each new event overwrites the oldest event
in the log. The events are listed in reverse chronological order. This screen includes the
following fields:
Timestamp
This is the date and time the event occurred.
Event
The message in this field describes the event. Possible events are:
Before/After Switching Delta Bad
The change in voltage (or kvars for var controls) before or after switching was unusually
low. See Instruction Sheet 1023-530, “S&C IntelliCap® Plus Automatic Capacitor
Control:
Setup
,” for more information.
Before/After Switching Delta OK
The change in voltage (or kvars for var controls) before or after switching returned to its
normal level.
Cap. Bank In Circuit
The capacitor control switched in the bank.
Cap. Bank Out of Circuit
The capacitor control switched out the bank.
Hardware Manual Override Disabled
The faceplate OPERATION MODE switch was set to
Automatic
mode.
Using IntelliLink Software to Locate Problems