8 S&C Instruction Sheet 1023-550
Power Problems
When the load fuse blows, the voltage magnitude the control displays will be
approximately zero.
NOTICE
Before changing a blown load fuse, set the operation mode to fthe
Manual setting . This
will prevent any automatic operation .
Follow these steps to check a blown load fuse:
STEP 1.
With the faceplate buttons, change the operation mode to the
Manual
state.
STEP 2.
Remove the fuse holder from the faceplate and replace the fuse. See Figure 1 on
page 7.
STEP 3.
Switch the bank in and out. If the new fuse blows, check the wiring, peripheral
equipment, and line switches.
Load Fuse Is Blown