S&C Instruction Sheet 1022-510
Figure 1. The current sensor installation (IntelliCap with Var only
control).
Detail notes for Figure 1:
1. Install the current sensor on the source side of the
capacitor bank connection.
2. The current sensor must be grounded at the top of the pole.
3. A dedicated potential transformer for control power
should be connected with one leg connected to the same
phase as the current sensor.
Installation