Instruction Sheet 766-546
S&C Compact IntelliRupter
®
PulseCloser
®
Fault Interrupter Quick Operating Guide
May 1, 2017
© S&C Electric Company 2013-2017, all rights reserved
Interrupter Open/Closed
Indicator
(one per pole)
Green:
Interrupter open—“O”
Red:
Interrupter closed—“I”
Colors are reversed on an IntelliRupter
fault interrupter furnished with Option
“-F2”
If status indicator is off:
•
Supply voltage to the External Power Supply (EPS) if it is not
energized.
•
If the EPS is energized, replace protection and control module.
If status indicator does not indicate
Wi-Fi connection:
•
If EPS is energized, move computer at least 20 feet closer.
•
Try another computer furnished with IntelliLink
®
Setup Software
and appropriate security keys.
•
Replace communication module.
If IntelliRupter
®
fault interrupter does not respond to
SCADA commands:
•
Enable remote operation (see “IntelliLink Setup Software
Operation—Main” screen). Remove all hot line tags and push up
on right interrupter open/close/ready lever.
•
Apply local hot line tag. If IntelliRupter fault interrupter does not
send a hot line tag status point to SCADA, replace communication
module.
Lower terminal pad (X)
Upper terminal pad (Y)
Interrupter Open/Close/Ready Lever
To open interrupters:
Pull down on right lever. In down position, closing is blocked.
To close interrupters:
Power must be available from the battery (if furnished) or energized
External Power Module. Remove hot line tags, if applicable. Push up
on right lever. Then pull down once on left lever for First Closing
Profile, or quickly pull down twice on left lever for Second Closing
Profile.
Pole 1
Pole 2
Pole 3
External power supply (see 766-512)
Communication
module
Hot Line Tag Lever
To manually apply a hot line tag:
Pull down on HOT LINE TAG lever.
To clear a manually applied hot line tag:
Push up on HOT LINE TAG lever.
To clear an electronically applied hot line
tag when a hot line tag has been applied
manually:
Push up on HOT LINE TAG lever. Then pull
down and push up on HOT LINE TAG lever
once, without delay.
To clear an electronically applied hot
line tag when a hot line tag has not been
applied manually:
Pull down and push up on HOT LINE TAG
lever twice, without delay.
Ground Trip Block Lever
(if furnished)
To manually apply ground trip block:
Pull down on GROUND TRIP BLOCK lever.
(When in the applied position the selected ele-
ments will be blocked or change as indicated
in the setup, see S&C Instruction Sheet 766-
530.)
To remove a manually applied GTB:
Push up on ground trip block lever. (Placing the
GROUND TRIP BLOCK lever in the up posi-
tion will not enable any elements that have not
been enabled in the active protection profile.)
Status Indicator
(white LED)
Flashes for ½ second every 30 seconds:
Normal operation
Pulsates dim to bright:
Wi-Fi connected
Flashes for ½ second every second:
Any Error State, or a Settings Mismatch is active
Flashes 3 times (½ second on—½ second off) every
30 seconds:
Loop Restoration is timing or Ready, or
IntelliTeam is Ready
On 10 seconds, then flashes for ½ second every
30 seconds:
Wi-Fi disconnected, open/close
command from interrupter open/close/ready lever,
Wi-Fi, or SCADA, or ground trip block lever moved
Solid On:
Remote Operation disabled
Off:
IntelliRupter fault interrupter not powered, or not
functioning properly
Protection and Control Module
Hot Line Tag Indicator
(amber LED
)
Flashes for ½ second every 2 seconds:
Hot line tag applied
Off:
All hot line tags removed
WARNING
IntelliRupter PulseCloser Fault Interrupter must be installed, operated, and maintained by qualified persons who are knowledgeable
in overhead electric power distribution equipment and the associated hazards. This guide is not a replacement for adequate train-
ing and experience in safety procedures for this type of equipment. Read S&C Instruction Sheets 766-510, 766-530, and 766-540
thoroughly and carefully before installing and operating your IntelliRupter PulseCloser Fault Interrupter.