S&C Instruction Sheet 765-500
17
Installation
Installing the Wildlife Disks:
Before installing the wildlife disks, determine
the proper placement of the disks on the switch
blade and contact insulators.
On 14.4-kV Omni-Rupter Switches
(Porcelain and Cypoxy® Insulators)
Install the wildlife disk to the bottom skirt root
of the insulator on both the blade and contact
ends of the switch. When the wildlife disks are
properly installed, the disks will overlap slightly
as shown in Figure 13.
On 25-kV Omni-Rupter Switches
(Porcelain and Cypoxy® Insulators)
Blade-end of the switch: Install the wildlife disk
on the bottom skirt root of the insulator.
Contact-end of the switch: Count up two
skirts from the base and install the wildlife disk
to the insulator on the blade-end. When the wild-
life disks are installed properly, they will be at
approximately the same height. See Figure 14.
Figure 14. Wildlife disk placement on 25-kV Omni-Rupter Switches.
Contact-end
Blade-end
Bottom
skirt
Disks at same height
Two skirts
from bottom
skirt
Insulator
Insulator
Figure 13. Wildlife disk placement on 14.4-kV Omni-Rupter Switches.
Disks overlap
blade-end over
contact-end
Bottom
skirt
Contact-end
Blade-end
Bottom
skirt
Insulator
Insulator
Summary of Contents for Omni-Rupter