627-500
15
INSTALLATION
Step 14
Apply resilient grout at the bottom of each
module to prevent entry of rodents, insects, or
weeds. It is recommended that the grouting be
recessed suffi ciently from the exterior exposure
to per m it cau l k i ng w it h a weat her proof
compound, applied with a standard caulking
gun. A room-temperature vulcanizing (RTV)
silicone rubber compound is recommended.
Step 15
O n mu lt i- modu le a s sembl ie s sh ipped i n
individual modules, align, level, center, check
door operation, grout, and caulk succeeding
modules in turn, and join modules with the
¹⁄₂
–13 galvanized bolts provided. The bolts
may be easily pressed through the gasketing
tape.
Do not attempt to draw misaligned
m o du l e s t oge t h e r w it h t h e se b o l t s
. See
Figure 8.
Figure 8. Alignment of PMX Switchgear modules.
This
Not this!