S&C Instruction Sheet 653- 502
21
Components and Controls
Operating Controls
Operating controls are located inside the switchgear bay. The controls consist of the
ENABLE/DISABLE toggle switch and the RESET pushbutton. See Figure 11 for the loca-
tion of the operation controls for the 250-kW and 500-kW systems and Figure 12 on page
22 for the 750-kW and 1000-kW systems.
ENABLE/DISABLE
–This toggle switch permits the operator to select whether the sys-
tem is enabled or disabled. With the switch in the
Enable
position, the system is enabled.
With the switch in the
Disable
position, the system is disabled. When the system is dis-
abled, the system will go to the
Bypass Isolate
state, connecting the utility to the load
though the bypass circuit breaker. The bypass circuit breaker will be closed and the input
and output isolation circuit breakers will be opened.
RESET
–This pushbutton allows the operator to manually reset the system alarm(s).
When the system is in the
Bypass
state and the RESET pushbutton is pushed, all latched
alarm(s) will be reset if the alarm(s) have cleared.
Figure 11. Location of operating controls for the 250-kW and 500-kW PureWave UPS Systems.
ENABLE/DISABLE switch
RESET pushbutton