10
S&C Instruction Sheet 461-500
Figure 5d. Inserting 15/27-kV TripSaver Dropout Recloser into
mounting.
Figure 5c. Inserting 15/27-kV TripSaver Dropout Recloser into
mounting.
Figure 5b. Inserting 15/27-kV TripSaver Dropout Recloser into
mounting.
Figure 5a. Inserting 15/27-kV TripSaver Dropout Recloser into
mounting.
Installation
b) Insert 15/27-kV TripSaver Dropout Recloser into
the mounting by hand as shown in Figures 5a and
5b. Ensure that the end of the trunnion slides under
the connector bracket, as shown in Figure 5d. This
allows the trunnion to be lowered into the hinge.
Alternately, insert the curled prong of an S&C Talon
Handling Tool or a distribution prong into the lifting
eye on the trunnion, and raise TripSaver Dropout
Recloser into the mounting. See Figures 5c and
5d. If a Talon tool is used, rotate the universal pole
counterclockwise 180° to disengage it.