12
S&C Instruction Sheet 461-500
Figure 8. DO NOT move the mode selector from AUTO to NR
position with TripSaver Dropout Recloser in dropout position.
Figure 7. Verifying mode selector handle is in AUTO position.
STEP 4.
Verify that the mode selector handle is in the
AUTO position. See Figure 7.
If the mode selector handle is in the NR position,
place the handle in AUTO position by hand. Alter-
nately, tap the mode selector using the straight
prong of an S&C Talon Handling Tool or a distribu-
tion prong, and verify that it reverts to the AUTO
position.
NOTICE
The mode selector handle must be placed in the AUTO
position before closing TripSaver Dropout Recloser into
the mounting . Closing TripSaver Dropout Recloser with
the mode selector handle in the NR position may result
in the unit tripping open due to inrush current .
DANGER
DO NOT
attempt to move the mode selector from the
AUTO position to the NR position while TripSaver Drop-
out Recloser is in the dropout position, as shown in
Figure 8 . This may result in TripSaver Dropout Recloser
making contact with the upper contact of the mounting,
causing arcing, serious injury, or death .
Installation
Summary of Contents for TripSaver
Page 24: ......