14
S&C Instruction Sheet 461-500
Operation
If TripSaver Dropout Recloser Has
Dropped Out
STEP 1.
Determine and resolve the cause of the fault.
STEP 2.
Verify that the mode selector handle is in the AUTO
position. See Figure 10.
Insert the straight prong of an S&C Talon Handling
Tool or a distribution prong into the mode selector
handle and place the handle in the AUTO position.
NOTICE
The mode selector handle must be placed in the AUTO
position before closing TripSaver Dropout Recloser into
the mounting. Closing TripSaver Dropout Recloser with
the mode selector handle in the NR position may result
in the unit tripping open due to inrush current.
DANGER
DO NOT
attempt to move the mode selector from the
AUTO position to the NR position while TripSaver
Dropout Recloser is in the dropout position as shown in
Figure 11. This may result in TripSaver Dropout Recloser
making contact with the upper contact of the mounting,
causing arcing, serious injury, or death.
Figure 10. Verifying mode selector handle is in AUTO position.
Figure 11. DO NOT move the mode selector from AUTO to
NR position with TripSaver Dropout Recloser in the dropout
position.