Sanden
Heat
Pump
–
Service
Technical
Book
Page
28
of
48
Check Points
Error
Code
Error Contents
Error Detection Condition &
Diagnostic
Connector
No. or
Maintenance
Monitor No.
Connector
Colour
Judgment & Repair Methods
E048
Defrost drive conducted while
ambient temperature thermistor
detected 20degC
㩷
㩷
㩷
㩷
<Check Items>
㩷
㩷
㩷
㩷
- Trouble in air absorption due to
foreign object blocking air path
through evaporator
㩷
㩷
- Remove foreign object from
evaporator
㩷
- Ambient temperature thermistor
malfunction
㩷
㩷
- Replace ambient temperatrue
thermistor
㩷
High Ambient
Temperature Defrost
Drive Error
- defrost thermistor malfunction
㩷
㩷
- Replace defrost temperatrue
thermistor
E070
Continuous fan motor abnormal
operation.
㩷
㩷
㩷
㩷
<Check Items>
CN12
White
㩷
㩷
- Fan blade rotated with foreign
object stuck on it
㩷
㩷
- Remove foreign object
㩷
- Fan motor locked
㩷
㩷
- Replace fan motor
㩷
- Check if connector is fallen out
or not connected properly
㩷
㩷
- Put it back on properly if it is not in
right position
㩷
Fan Motor Locked
- Fan motor malfunction
㩷
㩷
- Replace fan motor
E071
Continuous fan motor abnormal
operation.
㩷
㩷
㩷
㩷
<Check Items>
CN12
White
㩷
㩷
-Fan blade do not rotate
㩷
㩷
- Put it back on properly if it is not in
right position
㩷
-Fan blade rotates in higher
speed than usual
㩷
㩷
- Replace fan motor
㩷
Fan Motor Revolution
Error
- Fan motor malfunction
㩷
㩷
- Replace fan motor
E073
When less than 150rpm of water
circulation pump rotation detected
㩷
㩷
㩷
㩷
<Check Items>
㩷
㩷
㩷
㩷
- Check if pump connector is
fallen out or not connected
properly
CN13
Red
- Put it back on properly if it is not in
right position
㩷
Water Circulation Pump
Locked
- Water pump malfunction
㩷
㩷
- If rotation of water circulation pump
do not reach expected number of
rotation even after turning it on on the
timer setting panel, it is a malfunction
of the water circulation pump.
㩷
㩷
- Check for bends or blockings on
HP connection pipes
㩷
㩷
- Correct piping and remove bends
and blockings
E090
Error in clock IC writing or reading
㩷
㩷
㩷
㩷
Clock IC Error
㩷
㩷
㩷
- Try rebooting and if the same error
occurs again, PC board replacement
is necessary
Error detected on serial
communication driver
㩷
㩷
㩷
E101
㩷
㩷
㩷
㩷
Communication Error (to
inverter module)
<Check Items>
Error in compressor wiring
- Check resistance between 2
phases on compressor
compressor malfunction
㩷
㩷
㩷
㩷
㩷
㩷
㩷
㩷
㩷
- Correct compressor wiring
- Normal: PC board replacement
required
- Abnormal: Heat pump unit
replacement required
- Heat pump unit replacement
required