6002 and 6002-14B offer precision to assure the health and safety to occupants with the tightest possible controls on energy consumption. 
They are versatile, self-contained dual gas sensors that are network ready for either peer-to-peer (master slave) operation or central control 
for a smooth integration into new or existing energy management systems.

Applications:

•  Vehicle Emissions
•  Combustible Gases
•  Refrigerant Gas Leak Detection
•  Industrial Health and Safety

Features:

•  Stand-alone operation with 1 or 2 adjustable alarm relays, indicators and strobe
•  BACnet Laboratory (BTL) listed Smart Sensor, up to 76,800 baud
•  BACnet MS/TP RS485 interface
•  CAN network interface for master-slave operation or central control
•  Pre-calibrated plug-and-play sensor modules
•  Impact resistant, water resistant enclosure.

Specifications

:

•  Supply 24 vac 50/60 hz (17-28 vac) 0.21 amps, 5 va
•  Relays (1 or 2) SPDT, 5 amp @ 125 vac, non-inductive
•  On delay: 0-999 seconds (16 minutes)
•  Off delay: 0-999 seconds (16 minutes)
•  Operating temperature -20

º

 

C to 50

º

 

C (-4

º 

F to 122

º 

F)

•  For indoor use 
•  Flame resistant Polycarbonate ABS enclosure rated UL94 V0, 5VB, and 5VA
•  Standards.  Conforms to UL61010-1, CSA C22.2 61010-1-12, ANSI/ISA 61010-1, CSA C22.2 no. 205-12
•  Pollution degree 2
•  Installation category II
•  Altitude 2000m
•  Humidity max 90% rh. 90% to temperatures up to 31

º 

C (88 

º

 F), decreasing linearity to 50% rh at 40

º

C (104

º

F)

User Interface:

•  Back lit LCD display shows gas concentration, user settings, calibration controls
•  Red LED alarm indicators, gas level 1 and 2
•  High intensity white LED strobe on level 3
•  Audible alarm, 85 db at 1 meter
•  4 pushbutton user keypad
•  Password control for settings

Wiring

Summary of Contents for 6002

Page 1: ...Gas Detectors READ AND SAVE THESE INSTRUCTIONS The purpose of this manual is to aid in the proper installation and operation of fans manufactured by Soler Palau USA These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and types of fans manufactured by Soler Palau USA ...

Page 2: ......

Page 3: ...ated plug and play sensor modules Impact resistant water resistant enclosure Specifications Supply 24 vac 50 60 hz 17 28 vac 0 21 amps 5 va Relays 1 or 2 SPDT 5 amp 125 vac non inductive On delay 0 999 seconds 16 minutes Off delay 0 999 seconds 16 minutes Operating temperature 20º C to 50º C 4º F to 122º F For indoor use Flame resistant Polycarbonate ABS enclosure rated UL94 V0 5VB and 5VA Standar...

Page 4: ... configuration Make all chain connections at the sensors to avoid T connections 6 Move the end of line jumper the one above terminal 1 1 12 to the on position UP on the first sensor or controller on the chain and the last sensor controller on the chain A controller can be located anywhere on the chain Ensure its EOL jumper is off down if it is in the middle Any sensor controller address can be in ...

Page 5: ...stalled at 50 of the ceiling height and above the vehicle height If the exhaust pipes of diesel vehicles are below the vehicles then the nitrogen dioxide detectors should be installed at 3 to 5 feet 1 to 1 5 meters from the floor In all cases the detectors must be installed above obstructions blocking circulation of air in front of the detectors example maintenance garages in automobile dealership...

Page 6: ...ay on seconds 0 999 30 5 A2Off Alarm 2 Delay off seconds 0 999 20 6 AL3 Alarm 3 threshold sounder and strobe by sensor 7 A3Del Alarm 3 Delay on seconds 0 999 180 8 A3Off Alarm 3 Delay off seconds 0 999 20 9 A1Tx Alarm 1 transmit message CAN network 0 255 1 10 A1Tx Alarm 1 transmit message CAN network 0 255 1 1 A1Tx Alarm 1 transmit message CAN network 0 255 12 A2Tx Alarm 2 transmit message CAN net...

Page 7: ...a or 10V sensor B to tweak output for controller input errors Accessing this option forces output high for testing 44 Temp Temperature delay enable off on 0 1 0 45 Aud Local audio alarm enable on alarm 3 0 1 1 46 BAC BACnet MSTP mode select 0 BACnet communication disabled 1 BACnet communication enabled 2 BACnet communication enabled and display all sensors on CAN network 0 1 2 0 47 BMA BACnet MAC ...

Page 8: ...rises above the alarm setting 8 When the Delay Off Timer times out the relay 1 will de energize the Alarm 1 LED will turn off and the Relay 1 Transmit message will stop being sent thereby de energizing relays on other units 9 If the temperature exceeds the Hi Temperature Alarm setting 51 relay 1 will activate the Alarm 1 LED will turn on and the Alarm 1 Transmit message will be sent via the CAN ne...

Page 9: ...groups To control multiple zones on the same network set the transmit message on each sensor to different messages for different zones The default transmit messages are 1 2 3 for alarm levels 1 2 3 for zone 1 Set zone 2 sensors to transmit messages to 4 5 6 Set zone 3 sensors to transmit 7 8 9 and so on Addresses Set each sensor and controller to a different address setting 39 1 2 3 4 etc It is im...

Page 10: ...ng stops going up The span gas should must be within the range of sensor s scale 9 Adjust the reading to match the concentration in the bottle 10 Press and at the same time to save 1 1 If second sensor installed press and repeat steps 4 to 10 for sensor B 12 Press left arrow several times to return to settings and home Calibration Procedure for Refrigerant type 13 20 and VOC type 01 sensors 1 0 Us...

Page 11: ...when returned to our factory transportation prepaid Deterioration or wear by heat abrasive action chemicals improper installation or operation or lack of normal maintenance shall not constitute defects and are not covered by warranty The motor is warranted by the motor manufacturer for one 1 year If the motor becomes defective in the warranty period it should be taken to the nearest authorized mot...

Page 12: ...l or consequential damages including but not limited to loss of profits or revenue loss of use of the equipment or any associated equipment cost of capital cost of substitute equipment facilities or services down time costs or claims of customers of the purchaser for such damages Soler Palau USA neither assumes nor authorizes any persons to assume for it any other liability in connection with the ...