33
ENGLISH
Declaration of performance heat recovery unit BR 25 PLUS E
Supplier name or trade mark
S&P
S&P
S&P
Supplier Model Identi
fi
er and options installed
BR 25 PLUS E + 4BRF
BR 25 PLUS E +
RHRF / CO2RF
BR 25 PLUS E +
RHRF / CO2RF local
Reference climate
Temperate Cold
Hot Temperate Cold
Hot Temperate Cold
Hot
SEC in [kWh/(m²a)] per ogni tipo di clima (temperato,
caldo, freddo)
-31,28
-64,63 -9,54
-34,98
-69,56 -12,55
-39,32
-75,52 -15,95
SEC Class
A
A+
E
A
A+
E
A
A+
E
Declared Typology
UVR-B Bidirectional
UVR-B Bidirectional
UVR-B Bidirectional
Type of drive installed
Multi-speed drive
Variable speed
Variable speed
Type of heat recovery
Recuperative
Recuperative
Recuperative
Thermal ef
fi
ciency¹
73,3%
73,3%
73,3%
Maximum
fl
ow rate in [m³/h]²
250
250
250
Maximum electric Power in [W]
114
114
114
Sound Power Level (LWA) in [dB(A)]³
50
50
50
Reference
fl
ow rate [m
³
/h]
4
175
175
175
Reference pressure difference in [Pa]
50
50
50
SPI in [W/m
³
/h]
5
0,28
0,28
0,28
Control factor and typology
1
0,85
0,65
Declared maximum internal leakage [%]
6
0,7
0,7
0,7
Declared maximum esternal leakage [%]
6
1,5
1,5
1,5
1
Ef
fi
ciency according EN13141-7:2010 at reference
fl
ow at 50 Pa;
2
Maxiumum
fl
ow at 100 Pa external pressure;
3
Casing radiation at reference
fl
ow rate at 50 Pa external pressure;
4
Reference
fl
ow rate is 70% of maximum
fl
ow at 50 Pa external pressure according EN13141-7:2010;
5
According EN13141-7:2010 at reference
fl
ow rate;
6
According EN13141-7:2010;
SEC: Speci
fi
c Energy Consumption.