23. DEVICE ERROR MESSAGES
The control board installed inside the heat recovery unit has multi-color LED. In the event of a fault,
the corresponding fault code will be displayed with different color
fl
ashes. With the help of the
colors assumed by the signaling LED it is possible to search for the meaning of the relative error
message. Recognizing the sequence reproduced by the LED is useful for technical assistance in
recognizing the type of fault in progress. Below is a summary table of possible errors.
Indication pattern
Function
Binding mode is active (continuously green)
1
Normal mode (green LED flashes)
Exhaust fan error (1 X red; 1 X orange)
Supply fan error (1 X red; 2 X orange)
Emergency temperature stop (2 X red; 1 X orange)
X20 temperature sensor fault (2 X red; 2 X orange)
X21 temperature sensor fault (2 X red; 3 X orange)
X22 temperature sensor fault (2 X red; 4 X orange)
X23 temperature sensor fault (2 X red; 5 X orange)
RH sensor fault (3 X red; 3 X orange)
Pressure sensor ONE (3 X red; 2 X orange)
Pressure sensor TWO (3 X red; 1 X orange)
Identification
2
(orange LED flashes during 5 seconds)
Filter dirty (1 X green; 1 X red)
1
When the button is pressed the binding mode is ended.
2
Identi
fi
cation message received.
When there is an error the fault status is shown, the priority is from tacho to
fi
lter dirty with tacho
having the highest priority.
24. PUTTING OUT OF SERVICE AND RECYCLING
EEC legislation and our consideration of future generations mean that we should always
recycle materials where possible; please do not forget to deposit all packaging in the ap-
propriate recycling bins. If your device is also labeled with this symbol, please take it to the
nearest Waste Management Plant at the end of its servicable life.