7.3. FILTER INSTALLATION
The heat recovery is supplied with mounted fi lters.
On the extract air side, it is possible to install two fi lters in one fi lter holder, to create the desired com-
bination: G4+F7, F7+F9, M5+F7, etc...
To mount an additional fi lter, follow this procedure:
Installation two fi lters
1. Loosen the two sets of fi lter support brackets.
2. Remove the fi lter holder.
3. Fit the second fi lter ensuring that the direction of air is
correct (indicated in the frame of the fi lter).
4. Ensure that the fi rst fi lter the air passes is the lower
grade of fi ltration.
5. Once both fi lters have been through fi tted place the fi l-
ter supports symmetrically and tighten the 4 brackets.
7.4. RANGE SPECIFICATIONS
Model
Maximum
airfl ow
(m
3
/h)
D VERSIONS
Power supply
Max. absorbed current
(A)*
1
CADB-N 05 PRO-REG
470
230/1 Ph/50Hz
1,8
CADB-N 08 PRO-REG
780
230/1 Ph/50Hz
2,4
CADB-N 18 PRO-REG
1560
230/1 Ph/50Hz
2,4
CADB-N 30 PRO-REG
2630
230/1 Ph/50Hz
3,3
CADT-N 45 PRO-REG
4250
400/3Ph+N/50Hz
5,4
CADT-N 55 PRO-REG
5300
400/3Ph+N/50Hz
5,6
CADT-N 80 PRO-REG
8160
400/3Ph+N/50Hz
7,6
*
1
Heat recovery unit total (both fans).
Summary of Contents for CADB-N 05 PRO-REG
Page 2: ......
Page 15: ...15 ESPA OL Versi n DI con by pass Versi n DC con by pass Accesorio Accesorio Accesorio...
Page 49: ...49 ENGLISH DI Version with By pass DC Version with By pass Accessory Accessory Accessory...
Page 116: ...116 NEDERLANDS DI Version met By pass DC Version met By pass Accessoire Accessoire...
Page 137: ...137 21 ESQUEMAS EL CTRICOS WIRING DIAGRAMS SCHEMAS DE C BLAGE BEDRADINGSSCHEMA...
Page 138: ...138...
Page 139: ...139...
Page 140: ...140...
Page 141: ...141...
Page 142: ......
Page 143: ......