44
ENGLISH
8. CONTROL FUNCTIONS
FUNCTION
COMMENTS
1
Temperature regulation
Only versions with postheating batteries
incorporated (-DI/-DC)
2
Manual selection of speed: preset speed (slow/medium/high)
3
Automatic management of the fan speed by CO
2
or
HR sensors. VAV operation
Requires the sensor accessory
SCO2-A TERMO REG or SCO2-G TERMO-REG
4
Boost: Fans at full speed by external contact
Timed for 30 minutes.
To activate it the contacts need to be made
for at least 3 seconds
5
Automatic by-pass management
6
Preventing frost formation on the heat exchanger
7
Management of electrical battery of post-heating of 2 stages:
Stage control
8
Management of hot water coil of post -heating:
control 3 points
It is necessary the 3 way valve
3WP..3P 230 V
9
Management of hot water coil of post-heating:
proportional control
It is necessary the 3 way valve
3WV.. PROP 24V and TRAFO-15D
10
LED- Display status of the unit and alarms
11
Monitoring the status of the fi lters by differential pressure
switches
Included with the equipment supply
12
Monitoring fans status
9. CONTROL SCHEME
D Version with By-pass
Summary of Contents for CADB/T-N TERMO-REG Series
Page 2: ......
Page 16: ...16 ESPA OL Versi n DI con by pass Versi n DC con by pass...
Page 45: ...45 ENGLISH DI Version with By pass DC Version with By pass...
Page 74: ...74 FRAN AIS Version DI avec by pass Version DC avec by pass Accessoire Accessoire...
Page 91: ...91 ALIMENTACION 230V 50Hz CADB N D 12 18 23 30...
Page 92: ...92 ALIMENTACION 400V 50Hz 3Ph N CADT N D 45 55 80...
Page 93: ...93 ALIMENTACION 230V 50Hz CADB N DC C5 08...
Page 94: ...94 ALIMENTACION 230V 50Hz CADB N DC 12 18 23 30...
Page 95: ...95 ALIMENTACION 400V 50Hz 3Ph N CADB N DC 45 55 80...
Page 96: ...96 ALIMENTACION 230V 50Hz CADB N DI 05 08...
Page 97: ...97 ALIMENTACION 230V 50Hz CADB N DI 12...
Page 98: ...98 ALIMENTACION 400V 50Hz 3Ph N CADB N DI 18 23 30...
Page 99: ...99 ALIMENTACION 400V 50Hz 3Ph N CADT N DI 45 55 80...