55
ENGLISH
11. BOOST FUNCTION
By opening/closing the remote contact it is possible to disable / enable the Boost function. In this ope-
rating mode, the fans should be at maximum speed for a minimum time of 30 minutes. To activate the
Boost function it is necessary to activate the external contacts for al least 3 seconds. The Boost will
then be triggered for 30 minutes.
12. ANTI-FROST MANAGEMENT
Termo-Reg unit has a function preventing ice formation in the recovery unit which is activated when
the temperature of exhaust air drops down to 1ºC, in which case the procedure is as follows:
• First, open the By-pass to prevent condensation in the recovery unit, thereby preventing the forma-
tion of frost.
• The equipment continue to run for several minutes to be monitored continuosly the exhaust air
temperature. If this does not rise by 1ºC, the equipment will stop.
• After 15 minutes stopped, the equipment will automatically start up, cyclically repeating the above
steps.
13. ALARMS
When an error occurs, the Termo-Reg unit informs to the user with the status LED control terminal
equipment
. To know the error that is produced it is necessary to observe the LED on the contro-
ller located inside the control cabinet. This LED fl ashes regularly during normal operation.
13.1. ELECTRICAL CABINET OPENING WITH EQUIPMENT START UP
!
Danger of electrocution.
!
Any use that requires Access to the unit must be performed by qualifi ed personnel.
!
Access to the interior of cabinet is only to display the LED on the board. It is not necessary to
manipulate any internal components of the electrical panel.
The break switch of electrical panel incorporates a safety mechanism that prevents the opening of it in
the ON position, avoiding possible damage to outside installation during maintenance.
To proceed to open the panel with the equipment running in order to see the error displayed on the
Summary of Contents for CADB/T-N TERMO-REG Series
Page 2: ......
Page 16: ...16 ESPA OL Versi n DI con by pass Versi n DC con by pass...
Page 45: ...45 ENGLISH DI Version with By pass DC Version with By pass...
Page 74: ...74 FRAN AIS Version DI avec by pass Version DC avec by pass Accessoire Accessoire...
Page 91: ...91 ALIMENTACION 230V 50Hz CADB N D 12 18 23 30...
Page 92: ...92 ALIMENTACION 400V 50Hz 3Ph N CADT N D 45 55 80...
Page 93: ...93 ALIMENTACION 230V 50Hz CADB N DC C5 08...
Page 94: ...94 ALIMENTACION 230V 50Hz CADB N DC 12 18 23 30...
Page 95: ...95 ALIMENTACION 400V 50Hz 3Ph N CADB N DC 45 55 80...
Page 96: ...96 ALIMENTACION 230V 50Hz CADB N DI 05 08...
Page 97: ...97 ALIMENTACION 230V 50Hz CADB N DI 12...
Page 98: ...98 ALIMENTACION 400V 50Hz 3Ph N CADB N DI 18 23 30...
Page 99: ...99 ALIMENTACION 400V 50Hz 3Ph N CADT N DI 45 55 80...