background image

6

FIELD INSTALLED DUCT COLLARS

Ductwork Installation

All ductwork should be installed in accordance with local codes. The installing contractor is 
responsible for adherence to codes and restrictions. Generally, the duct system will perform best 
and will ensure easy installation if installed in the most direct and simple manner.

NFPA-96 requires that the exhaust duct must be installed using 16-gauge carbon steel or 
18-gauge stainless steel with all joints and seams welded liquid tight. Listed factory-built grease 
duct is an exception when installed according to manufactures instructions. NFPA-96 further 
requires that a minimum of 500 FPM (Feet Per Minute) velocity must be maintained in the exhaust 
duct. There is not a specified maximum however, exhaust velocity should not exceed 2200 FPM. 
Install access panels where required. In any event, conformance to local codes must be adhered 
to, unless variance is obtained.

Make-up air ductwork should contain adequate filtering provisions somewhere in the system 
before it is introduced into kitchen space, or in the hood. Select hood models require a make-up 
air fire damper with fusible link installed at the collar. Access to the fusible link must be installed in 
supply duct. Only use rigid type duct for make-up air. Do not use “flex” duct. This duct should be 
in accordance with project specifications and installed in accordance with standard SMACNA 
Low Pressure requirements.

Field Installed Duct Collars

When ordered, exhaust and supply collars are shipped loose (not connected to hood) and 
intended to be field installed on some projects. Determine the location of exhaust/supply collar(s). 
Collars should be located as close to center (left to right with a max. offset of one fourth the 
total length) of hood as possible. When two exhaust and/or supply collars are required, equal 
distance between collars (left to right) should be maintained. Loose collars are tack welded to top 
of hood (back of crate). Break tack welds to remove collars.  Exhaust collars must be folded up 
before installing. Fire Dampers are shipped loose inside the crate.

Exhaust Collars

For collar to duct connection see “Exhaust Duct Systems” Chapter 7 of NFPA-96. 
For field installed duct collars see above.

Supply Collars

Install make-up air duct per local standard. For field installed duct collars, see above.

Important:

 Refer to your AHJ (Authority Having Jurisdiction) for requirements and/or questions 

on local codes.

Clearance to Combustible Materials

A further note on ductwork is important. Please consult NFPA-96 4.2 Clearance. An 18 in. 
clearance is required for unprotected combustible material. This clearance may be reduced if 
the combustible material is protected by an engineered construction system acceptable to the 
authority having jurisdiction, or by the use of materials or products listed for protection purposes 
Consult NFPA-96 and local codes before installing any hood system or exhaust ductwork.

Summary of Contents for JENcoFAN EO

Page 1: ...tion of fans manufactured by S P USA These instructions are intended to supplement good general practices and are not intended to cover detailed instruction procedures because of the wide variety and...

Page 2: ...ts are met Contact your local representative should you need further information SHIPMENT AND RECEIVING Prior to shipment all fans have been thoroughly inspected and tested All equipment shipped from...

Page 3: ...consent of its Jacksonville Florida office The foregoing shall constitute our sole and exclusive warranty and our sole and exclusive liability and is in lieu of all other warranties whether written o...

Page 4: ...vane anemometer across the filter bank Multiply the average velocity by the cross sectional area of the duct in square feet or by the net free area of the filter bank If the airflow as measured is no...

Page 5: ...Filters in fan clogged Clean filters and replace Fire system not armed or has been activated Ensure micro switch on fire system is wired properly Arm fire system Hood Not Capturing Smoke Dirty grease...

Page 6: ...ed in accordance with standard SMACNA Low Pressure requirements Field Installed Duct Collars When ordered exhaust and supply collars are shipped loose not connected to hood and intended to be field in...

Page 7: ...greasing with a food grade high temperature silicone Clean grease extractors daily in a dishwasher or other containers with a mild detergent in warm hot water Never use harsh or abrasive cleaners on s...

Page 8: ...8 END TO END CONFIGURATION...

Page 9: ...9 BACK TO BACK CONFIGURATION...

Page 10: ...10 GREASE TROUGH AND CUP INSTALLATION...

Page 11: ...1 1 HOOD OPTIONS 1 1 BACK RETURN PLENUM...

Page 12: ...12 HOOD OPTIONS 1 2 FRONT PERFORATED SUPPLY PLENUM FPSP...

Page 13: ...13 HOOD OPTIONS 1 3 STAINLESS STEEL WALL SPLASH PANELS...

Page 14: ...14 HOOD OPTIONS 1 4...

Page 15: ...15...

Page 16: ...S P USA Ventilation Systems LLC 6393 Powers Avenue Jacksonville FL 32217 T 904 731 4711 F 904 737 8322 www solerpalau usa com...

Reviews: