7
3.2. ACCESSORIES
Item no.
Description
5800018800
NEMBUS-VOC
VOC-Sensor
5800017800
SABIK-NEMBUS-SF
Servoflow (constant airflow kit)
5800018200
NEMBUS210-PH (Pre heater)
5800016200 SPCM
Communications module
5800015700
DSI (dry siphon)
3.3. REPLACEMENT PARTS
Item no.
Description
R153120101
NEMBUS 210-M1 scroll/ventilator unit
R153120007
NEMBUS 210-M2 scroll/ventilator unit
R153120016
NEMBUS 210-PL main PCB
R153120023
NEMBUS 210-FA Filter cover
R153120037
NEMBUS 210-TFF humidity/
temperature sensor
R153120009
NEMBUS 210-HRPTC Preheater
module w/o PCB
R153139302
NEMBUS 210-WT Heat exchanger
R153139052
SABIK-NEMBUS-HRE Preheater PCB
R153139024
SABIK-NEMBUS-FB Remote control
4. TECHNICAL DATA
4.1. CONDITIONS FOR INSTALLATION
Ambient temperature
installation site
+12°C to +40°C
Minimum outdoor air
temperature (Including
preheating radiator [optional
accessory])
-15°C
Environmental conditions
Non-saline, no
aggressive chemicals,
no risk of explosion
4.2. DEVICE DATA
Weight
32 kg
Material
Powder coated sheet metal
Connection for
condensate
DN20
Supply voltage
230 V AV, 50/60 Hz
Safety plug
Max. power input
P
max.
= 82 W, I
max.
0.8 A
Nominal airflow rate
(extract air)
160 m³/h at 100 Pa
Speed regulation
Four speeds
Direct-current fans
2 pieces, backwardcurved
impeller DN 190 EC
Counterflow heat
exchanger
Plastic
Filter
Filter quality extract air side:
• ISO Coarse 65% (G4)
Filter quality supply air side:
• ISO Coarse 65% (G4)
• Optional: ISOePM1 70% (F7)
Control panel
With cables
Weekly timer
Four pre-set programmes
Protection class
IP21
4.3. EFFICIENCY
EN 13141-7
PHI
83.4%
82.2%
4.4. SPEEDS
Factory setting
Fan speed V1
Humidity protection (40%)
Fan speed V2
Reduced ventilation (70%)
Fan speed V3
Nominal air (100%)
Intensive ventilation
Intensive ventilation (130%)
4.5. SERIAL NUMBER
9
M+P-26A-2273
74
The serial number is located on the nameplate next to
the condensate connection (9).